Installation and Maintenance Manual
Installation Mechanical
RTAE-SVX001B-EN 23
Compressor Shipping Bolt Removal
Units with InvisiSound™ Ultimate Option
(Model Number Digit 12 = 3)
For chillers built with InvisiSound Ultimate option,
compressor shipping bolts must be removed to assure
minimum noise during operation. Use a 24mm socket to
remove the (3) M15 x 75mm shipping bolts for each
compressor.They are located under compressor
mounting feet. See Figure 15.
Important:
• DO NOT DISCARD SHIPPING BOLTS. Store bolts in the
control panel for future use.
• All shipping bolts MUST be reinstalled prior to
compressor removal or unit move.
Drainage
Locate the unit near a large capacity drain for water vessel
drain-down during shutdown or repair. Evaporators are
provided with drain connections. A vent on top of
evaporator waterbox prevents vacuum by allowing air into
evaporator for complete drainage. All local and national
codes apply.
Table 13. Isolator selections
Location
Tons 1 2 3 4 5 6 7 8 9 10
Standard Length Unit
150S Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 - - - -
165S Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 - - - -
150 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
165 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
180 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
200 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
225 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
250 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
275 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
300 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
Extended Length Unit
(a)
150S Red 62 Red 62 Green 63 Green 63 Green 63 Red 62 - - - -
165S Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 - -
150 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
165 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
180 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
200 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
225 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
250 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
275 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
300 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
(a) Units are extended length if either of the following are selected:
Low Harmonic Distortion Option (model number digit 29 = 1)
Autotransformer (model number digit 28 = 1 or 2)
Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.
NOTICE:
Equipment Damage!
Do not remove compressor or move unit without
reattaching compressor shipping bolts. Failure to
reinstall bolts could cause shifting of parts and result in
equipment damage.
Figure 15. Compressor shipping bolt removal
Compressor
Shipping Bolt
Compressor
Mounting
Foot
Isolator