RLC-PRC042D-EN 29
Electrical
Table 6. Customer wire selection
(a)
— 50 Hz
(a)Field wire insulation temperature rating must be minimum 90°C unless otherwise specified.
Unit Size Volt Terminal Block Circuit Breaker Circuit Breaker - High Fault
150
380 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
165
380 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
150
380 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
165
380 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
180
380 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
200
380 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
225
380 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
250
380 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
275
380 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
300
380 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM