Catalogue
28 RLC-PRC042D-EN
Electrical
250
200 (4) 2 AWG - 600MCM n/a (4) 3/0 AWG - 500MCM
230 (4) 2 AWG - 600MCM n/a (4) 3/0 AWG - 500MCM
380 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
460 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
575 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
275
200 (4) 2 AWG - 600MCM n/a (4) 3/0 AWG - 500MCM
230 (4) 2 AWG - 600MCM n/a (4) 3/0 AWG - 500MCM
380 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
460 (2) 4 AWG - 500MCM (2) 4/0 AWG - 500MCM (2) 4/0 AWG - 500MCM
575 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
300
200 (4) 2 AWG - 600MCM n/a (4) 2 AWG - 600MCM
230 (4) 2 AWG - 600MCM n/a (4) 2 AWG - 600MCM
380 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
400 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
460 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
575 (2) 4 AWG - 500MCM (3) 3/0 AWG - 500MCM (3) 3/0 AWG - 500MCM
(a)Field wire insulation temperature rating must be minimum 90°C unless otherwise specified.
Table 5. Customer wire selection
(a)
— 60 Hz (continued)
Unit Size Volt Terminal Block Circuit Breaker Circuit Breaker - High Fault