Catalogue
26 RLC-PRC042D-EN
Electrical
Table 4. Electrical data — 50 Hz — all ambients
AFD Input Amps Fans Control VA
(a)
Unit
Size
Rated
Voltage
(b)
Comp A Comp B Qty
(c)
kW FLA
Without
Harmonic Filtration
(model # digit 29 =X)
With
Harmonic Filtration
(model # digit 29 =1) MCA
(d)
MOP
(e)
150S 380/50/3 268 - 8 2.05 3.3 574 - 365 600
400/50/3 254 - 8 2.05 3.1 574 - 347 500
165S 380/50/3 285 - 10 2.05 3.3 574 - 393 600
400/50/3 270 - 10 2.05 3.1 574 - 373 600
150 380/50/3 151 151 8 2.05 3.3 894 1394 369 500
400/50/3 143 143 8 2.05 3.1 894 1394 350 450
165 380/50/3 157 157 10 2.05 3.3 894 1394 392 500
400/50/3 150 150 10 2.05 3.1 894 1394 372 500
180 380/50/3 173 173 10 2.05 3.3 894 1394 427 600
400/50/3 165 165 10 2.05 3.1 894 1394 405 500
200 380/50/3 186 186 12 2.05 3.3 894 1394 463 600
400/50/3 177 177 12 2.05 3.1 894 1394 440 600
225 380/50/3 194 194 12 2.05 3.3 934 1434 480 600
400/50/3 184 184 12 2.05 3.1 934 1434 455 600
250 380/50/3 225 225 12 2.05 3.3 934 1434 551 700
400/50/3 213 213 12 2.05 3.1 934 1434 523 700
275 380/50/3 241 241 14 2.05 3.3 934 1434 593 800
400/50/3 229 229 14 2.05 3.1 934 1434 563 700
300 380/50/3 260 260 16 2.05 3.3 934 1434 643 800
400/50/3 247 247 16 2.05 3.1 934 1434 610 800
(a)Control VA includes operational controls only. It does not include evaporator heaters. A seperate 115/60/1, 15 amp customer provided power connection is
required to power the evaporator heaters (150T-165T; 800 watts, 180T-300T; 1200 watts).
(b)Voltage Utilization Range: +/- 1-% of Rated voltage (use range): 200/60/3 (180-220), 230/60/3 (208-254), 380/60/3 (342-418), 400/60/3 (360-440),
400/50/3 (360-440), 460/60/3 (414-506), 575/60/3 (516-633)
(c) Number of fans is evenly distributed between the two chiller circuits.
(d)MCA - Minimum Circuit Ampacity - 125 percent of largest compressor VFD input plus 100 percent of all other loads
(e) Max fuse or MOPD = 225 percent of largest compressor VFD input plus 100 percent of second compressor VFD input, plus sum of condenser fan FLA.