Catalogue

RLC-PRC042D-EN 25
Electrical
225
200/60/3 160 160 12 2.05 2.7 1434 - 933 1200
230/60/3 160 160 12 2.05 2.7 1434 - 792 1000
380/60/3 194 194 12 2.05 3.3 934 1434 480 600
400/60/3 184 184 12 2.05 3.1 934 1434 455 600
460/60/3 160 160 12 2.05 2.7 934 1434 396 500
575/60/3 160 160 12 2.05 2.7 1434 - 317 450
250
200/60/3 186 186 12 2.05 2.7 1434 - 1071 1200
230/60/3 186 186 12 2.05 2.7 1434 - 909 1200
380/60/3 225 225 12 2.05 3.3 934 1434 551 700
400/60/3 213 213 12 2.05 3.1 934 1434 523 700
460/60/3 186 186 12 2.05 2.7 934 1434 455 600
575/60/3 186 186 12 2.05 2.7 1434 - 364 500
275
200/60/3 199 199 14 2.05 2.7 1434 - 1153 1600
230/60/3 199 199 14 2.05 2.7 1434 - 978 1200
380/60/3 241 241 14 2.05 3.3 934 1434 593 800
400/60/3 229 229 14 2.05 3.1 934 1434 563 700
460/60/3 199 199 14 2.05 2.7 934 1434 489 600
575/60/3 199 199 14 2.05 2.7 1434 - 392 500
300
200/60/3 215 215 16 2.05 2.7 1434 - 1250 1600
230/60/3 215 215 16 2.05 2.7 1434 - 1061 1200
380/60/3 260 260 16 2.05 3.3 934 1434 643 800
400/60/3 247 247 16 2.05 3.1 934 1434 610 800
460/60/3 215 215 16 2.05 2.7 934 1434 531 700
575/60/3 215 215 16 2.05 2.7 1434 - 425 600
(a)All 200, 230 and 575V units consist of a voltage autotransformer with a 460V unit downstream. As a result, AFD input amp draws for these voltages are
the same as those of a corresponding 460V unit.
(b)Control VA includes operational controls only. It does not include evaporator heaters. A separate 115/60/1, 15 amp customer provided power connection
is required to power the evaporator heaters (150T-165T; 800 watts, 180T-300T; 1200 watts).
(c) Voltage Utilization Range: +/- 1-% of Rated voltage (use range): 200/60/3 (180-220), 230/60/3 (208-254), 380/60/3 (342-418), 400/60/3 (360-440),
400/50/3 (360-440), 460/60/3 (414-506), 575/60/3 (516-633)
(d)Number of fans is evenly distributed between the two chiller circuits.
(e) MCA - Minimum Circuit Ampacity - 125 percent of largest compressor VFD input plus 100 percent of all other loads for 380V, 400V, and 460V incoming
voltage. All other voltages need to have the 460V calculation reflected to the appropriate voltage.
(f) Max fuse or MOPD = 225 percent of largest compressor VFD input plus 100 percent of second compressor VFD input, plus sum of condenser fan FLA.
Table 3. Electrical data — 60 Hz — all ambients (continued)
AFD Input
Amps
(a)
Fans Control VA
(b)
Unit
Size
Rated
Voltage
(c)
Comp A Comp B Qty
(d)
kW FLA
Without
Harmonic Filtration
(model # digit 29 =X)
With
Harmonic Filtration
(model # digit 29 =1) MCA
(e)
MOP
(f)