Figure 59 illustrates a basic actuator failure routine. Some changes are 
necessary when automatic self-testing is added to the program. The 
different ways of controlling an actuator have different means of resetting 
a failure. The failure reset is automatic if a failure is discovered during an 
automatic smoke alarm response or manual override from the smoke 
control panel. The failure indication is only maintained while there is a 
failure. On the other hand, the triggering of a system self-test, either 
scheduled or manual, will reset any failures discovered during a previous 
system self test. 
Figure 60 and Figure 61 on page 111 show the changes 
necessary to any dedicated system failure test routine. In either case, the 
connected BCU should be programmed to store the actuator failure in the 
alarm log.
Binary variable 21 goes true for a minimum of 10 seconds whenever a 
system self-test is triggered (see 
Figure 56 on page 106). This will reset 
any stored failures from a previous system self-test. 
Figure 60.  ast actuator fail checka 3-13-06