Programming Guide

VAV-SVP01A-EN 95
Troubleshooting
If sensor and receiver still do not operate properly, replace bad components. If unit passes
tests, check VV550 operation.
4. Defective VAV VV550
Disconnect the receiver sensor wires on the VAV VV550 on terminals TB3-1 and TB3-2 and
measure the VDC. It should be 5VDC. If 5VDC is not present check incoming power to the VAV
VV550 Controller board on TB1-1 and TB1-2. Should measure 24VAC ± 10%. If you measure
the proper voltage at TB1-1 and TB1-2 and no voltage at TB3-1and TB3-2 replace VV550.
Note: If no voltage at TB1-1 and TB1-2, see VV550 failure procedures
Disconnect the receiver sepoint wires on the VAV VV550 on terminals TB3-2 and TB3-3 and
measure the VDC. It should be 5VDC. If 5VDC is not present check incoming power to the VAV
VV550 Controller board on TB1-1 and TB1-2. Should measure 24VAC ± 10%. If you measure
the proper voltage at TB1-1 and TB1-2 and no voltage at TB3-2and TB3-3 replace VV550.
Table 26. Signal quality: LED1, LED2, LED3 on the sensor
User Action LED Display Indicates…
None LED1:Off
LED2:Off
LED3:Off
Normal state
* No Test button press
Press Test
Button (SS)
LED1:Off
LED2:Off
LED3:Off
Associated; no communication with receiver
* Associated, but no signal from the receiver after
pressing Test button
LED1:On
LED2:On
LED3:On
Displays for 5 seconds, then constantly off
Excellence signal quality
* Adequate signal margin for reliable communication.
LED1:Off
LED2:On
LED3:On
Displays for 5 seconds, then constantly off
Marginal signal quality
* Reduced battery life is likely.
* Consider moving the sensor or receiver to a better
location.
LED1:Off
LED2:Off
LED3:On
Displays for 5 seconds, then constantly off
Poor signal quality
* Unreliable communication.
* Strongly recommend moving the sensor or receiver to
a better location.
Table 27. Signal quality: LED1, LED2, LED3 on the receiver
User Action LED Display Indicates…
None
LED1:Off
LED2:Off
LED3:Off
Normal state
* No Test button press
Press Test
Button (SS)
LED1:On
LED2:On
LED3:On
Displays for 5 seconds, then constantly off
Excellence signal quality
* Adequate signal margin for reliable communication.
LED1:Off
LED2:On
LED3:On
Displays for 5 seconds, then constantly off
Marginal signal quality
* Reduced battery life is likely.
* Consider moving the sensor or receiver to a better
location.
LED1:Off
LED2:Off
LED3:On
Displays for 5 seconds, then constantly off
Poor signal quality
* Unreliable communication.
* Strongly recommend moving the sensor or receiver to
a better location.