Programming Guide
54 VAV-SVP01A-EN
VAV VV550 Controller Device Home Tabs: Instructions
Chapter Overview
This chapter contains information about the following:
• Setpoints Tab
•Unit Tab
•Setup Tab
• Inputs Tab
•Outputs Tab
•Test Tab
•Other Tab
Configuration
To access the data fields for each tab and to make adjustments, select the Configure button. To
make adjustments, find the correct parameter, change it, and download to VV550.
Setpoints Tab
In Rover, the setpoints can be changed by selecting the Configure button. Following are
descriptions of each line on the Setpoints tab.
Default Setpoints
Unoccupied Cooling: Set points have a range of 30.0° - 100.0°F (-1.1° - 37.8°C). This cooling set
point is used when the VAV VV550 Controller is unoccupied. The unoccupied cooling set point must
be greater than or equal to the unoccupied heating set point plus 2.0°F 1.1°C).
Figure 42. Setpoints tab