Programming Guide
46 VAV-SVP01A-EN
VAV VV550 Controller Programming and Operation
Pressure independent control - When a valid flow value is present, the controller operates under
pressure independent control. If after an airflow sensor failure, the airflow returns to the valid range
(airflow value greater than 10% of configured nominal airflow), the controller automatically
resumes pressure independent control.
Initiate Calibration button: The calibration sequence enables the controller to calibrate the air
valve position and the water valve position.
Unit Description
Describes the type of device being communicated to via Rover service tool. It also indicates the
general program that has been placed in controller.
Outputs Tab
Fan Status: The Fan will be shown as On, Off, or None.
Air Valve Position: Indicates air valve or damper position.
Reheat Capacity: Will indicate reheat capacity in Percentage.
Figure 34. Outputs tab