Programming Guide

VAV-SVP01A-EN 39
VAV Start Up/Check Out Procedure
4. Review the display to ensure that you have selected the correct configuration options.
To return the display to operating mode, press the configuration button (See Step 1).
Note: The sensor will revert to operating mode if no buttons are pressed for 10 minutes.
The following example shows a configured display in operating mode.
If an error exists, it appears at the bottom of the display between the occupancy symbols, as shown
in below. SeeTable 20, p. 92 for error code definitions.
Figure 22. Configuration options
The example shows a display that has been configured for:
Dual setpoint
Temperature units (Fahrenheit)
Temperature resolution to tenths of a degree
System settings: Heat, Cool, Off
Fan Settings: Auto and On
Occupied/unoccupied option enabled
Figure 23. Display
Display shows the following:
Temperature units (Fahrenheit)
Temperature resolution to tenths of a degree
System setting: Cooling
Fan Setting: Auto
Occupied/Unoccupied option enabled
Figure 24. Error message