Programming Guide

VAV-SVP01A-EN 37
VAV Start Up/Check Out Procedure
3. Configure the sensor options in the order shown in the table.
Press or to scroll to the next selection.
Press or to move to the next menu.
Figure 20. Center button
Center button
Figure 21. Wireless configuration
Setting Configuration options
Temperature
Choose Fahrenheit or
Celsius
Choose the degree
resolution (whole degrees,
half degrees, or tenths of
degrees).
Setpoint
Deadband (available for dual
setpoint system only)
Note: Deadband refers to the
minimum difference
between the heating and
cooling setpoints.
System
a) Single setpoint
. .
.
.
.
.
dual setpoint
no
setpoint
single
setpoint
.
heat/cool setpoint offset
(1.8˚F – 10.8˚F, 1˚C – 6˚C)