Programming Guide

26 VAV-SVP01A-EN
VAV Start Up/Check Out Procedure
Ventilation Flow control
See Auxiliary Duct Temperature Sensor wiring on Space temperature controller Analog Inputs
Note: If heat is installed Auxilary sensor will be located at the discharge of the VAV unit.
Flow Tracking Control
Two controls are used in Flow tracking controller. One is configured with the Space temperature
control program and the other controller will be set up as flow tracking controller and it will not
need any input or output device connected to the controller. See Operation section for details.