Installation and Maintenance Manual

Table Of Contents
Installation - Electrical
90 RLC-SVX09H-EN
200
200
1 760 N/A #4-500
(a)
600 N/A 3/0-500
(a)
700 N/A #1-500 700 N/A #1-500
2 380 N/A #4-500 400 N/A 3/0-500
(a)
500 N/A 3/0-500
(a)
500 N/A 3/0-500
(a)
230
1 760 N/A #4-500
(a)
600 N/A 3/0-500
(a)
600 N/A 3/0-500
(a)
600 N/A 3/0-500
(a)
2 380 N/A #4-500 250 N/A #6-350 400 N/A 3/0-500
(a)
400 N/A 3/0-500
(a)
380
1 380 #4-500 #4-500 400 3/0-500
(a)
3/0-500
(a)
350 3/0-500
(a)
3/0-500
(a)
350 3/0-500
(a)
3/0-500
(a)
2
XL 380
YD 175
#4-500 #14-2/0 250 #6-350 #6-350 250 #6-350 #6-350 250 #6-350 #6-350
460
1 380 #4-500 #4-500 250 #6-350 #6-350 300 3/0-500
(a)
3/0-500
(a)
300 3/0-500
(a)
3/0-500
(a)
2 175 #14-2/0 #14-2/0 250 #6-350 #6-350 225 #6-350 #6-350 225 #6-350 #6-350
575
1 380 #4-500 #4-500 250 #6-350 #6-350 250 3/0-500
(a)
3/0-500
(a)
N/A N/A N/A
2 175 #14-2/0 #14-2/0 100 #10-1/0 #10-1/0 175 #6-350 #6-350 N/A N/A N/A
220
200
1 760 N/A #4-500
(a)
600 N/A 3/0-500
(a)
800 N/A #1-500
(b)
800 N/A #1-500
(b)
2 380 N/A #4-500 400 N/A 3/0-500
(a)
500
600
N/A 3/0-500
(a)
500
600
N/A 3/0-500
(a)
230
1 760 N/A #4-500
(a)
600 N/A 3/0-500
(a)
700 N/A #1-500
(b)
700 N/A #1-500
(b)
2 380 N/A #4-500
250
400
N/A
#6-350
3/0-500
(a)
400
500
N/A 3/0-500
(a)
400
500
N/A 3/0-500
(a)
380
1 380 #4-500 #4-500 400 3/0-500
(a)
3/0-500
(a)
450 3/0-500
(a)
3/0-500
(a)
450 3/0-500
(a)
3/0-500
(a)
2
XL 380
YD 175
380
#4-500
#14-2/0
#4-500
250 #6-350 #6-350
250
300
#6-350
3/0-500
(a)
#6-350
3/0-500
(a)
250
300
#6-350
3/0-500
(a)
#6-350
3/0-500
(a)
460
1 380 #4-500 #4-500 400 3/0-500
(a)
3/0-500
(a)
350 3/0-500
(a)
3/0-500
(a)
350 3/0-500
(a)
3/0-500
(a)
2
XL 175
380
YD 175
#14-2/0
#4-500
#14-2/0
#14-2/0 250 #6-350 #6-350
225
250
#6-350 #6-350
225
250
#6-350 #6-350
575
1 380 #4-500 #4-500 250 #6-350 #6-350 300 3/0-500
(a)
3/0-500
(a)
N/A N/A N/A
2 175 #14-2/0 #14-2/0
100
250
#10-1/0
#6-350
#10-1/0
#6-350
175
200
#6-350 #6-350 N/A N/A N/A
250
200
1 760 N/A #4-500
(a)
700 N/A #1-500
(b)
800 N/A #1-500
(b)
800 N/A #1-500
(b)
2 380 N/A #4-500 400 N/A 3/0-500
(a)
600 N/A 3/0-500
(a)
600 N/A 3/0-500
(a)
230
1 760 N/A #4-500
(a)
600 N/A 3/0-500
(b)
800 N/A #1-500
(b)
800 N/A #1-500
(a)
2 380 N/A #4-500 400 N/A 3/0-500
(a)
500 N/A 3/0-500
(a)
500 N/A 3/0-500
(a)
380
1 380 #4-500 #4-500 400 3/0-500
(a)
3/0-500
(a)
450 3/0-500
(a)
3/0-500
(a)
450 3/0-500
(a)
3/0-500
(a)
2 380 #4-500 #4-500 250 #6-350 #6-350 300 3/0-500
(a)
3/0-500
(a)
300 3/0-500
(a)
3/0-500
(a)
460
1 380 #4-500 #4-500 400 3/0-500
(a)
3/0-500
(a)
400 3/0-500
(a)
3/0-500
(a)
400 3/0-500
(a)
3/0-500
(a)
2
XL 380
YD 175
#4-500 #14-2/0 250 #6-350 #6-350 250 #6-350 #6-350 250 #6-350 #6-350
575
1 380 #4-500 #4-500 250 #6-350 #6-350 300 3/0-500
(a)
3/0-500
(a)
N/A N/A N/A
2 175 #14-2/0 #14-2/0 250 #6-350 #6-350 200 #6-350 #6-350 N/A N/A N/A
Notes:
1. Optional non-fused disconnect and circuit breaker.
2. Copper wire only, based on nameplate minimum circuit ampacity (MCA).
3. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.
4. Circuit two information is the same as circuit one unless listed on a separate line below circuit one values.
5. XL - across-the-line starter and YD - wye-delta starter.
(a) Will accept 2 conduits per phase in this size.
(b) Will accept 3 conduits per phase in this size.
Table 80. Customer Wire Selection - RTWD - 60 Hz - high efficiency - standard condensing temperature (continued)
Size
Rated
Voltage
#
Conn
Wire Selection
Main Terminal Block Disconnect Circuit Breaker Hi-Fault Panel Ckt Brkr
Size Wire Range Size Wire Range Size Wire Range Size Wire Range
Amp XL YD Amp XL YD Amp XL YD Amp XL YD