Installation and Maintenance Manual

Table Of Contents
Installation - Electrical
RLC-SVX09H-EN 87
130
200
1 380 N/A #4-500 400 N/A 3/0-500
(a)
500 N/A 3/0-500
(a)
500 N/A 3/0-500
(a)
2 380 N/A #4-500 250 N/A #6-350 350 N/A 3/0-500
(a)
350 N/A 3/0-500
(a)
230
1 380 N/A #4-500 400 N/A 3/0-500
(a)
450 N/A 3/0-500
(a)
450 N/A 3/0-500
(a)
2
175
380
N/A
#14-2/0
#4-500
250 N/A #6-350 300 N/A 3/0-500
(a)
300 N/A 3/0-500
(a)
380
1 380 #4-500 #4-500 250 #6-350 #6-350 250 #6-350 #6-350 250 #6-350 #6-350
2 175 #14-2/0 #14-2/0 250 #6-350 #6-350
200
175
#6-350 #6-350
200
175
#6-350 #6-350
460
1 380 #4-500 #4-500 250 #6-350 #6-350 225 #6-350 #6-350 225 #6-350 #6-350
2 175 #14-2/0 #14-2/0 100 #10-1/0 #10-1/0 150 #6-350 #6-350 150 #6-350 #6-350
575
1 380 #4-500 #4-500 250 #6-350 #6-350 175 #6-350 #6-350 N/A N/A N/A
2 175 #14-2/0 #14-2/0 100 #10-1/0 #10-1/0 125 #6-350 #6-350 N/A N/A N/A
140
200
1 760 N/A #4-500
(a)
600 N/A 3/0-500
(a)
600 N/A 3/0-500
(a)
600 N/A 3/0-500
(a)
2 380 N/A #4-500 250 N/A #6-350
350
450
N/A 3/0-500
(a)
350
450
N/A 3/0-500
(a)
230
1 380 N/A #4-500 400 N/A 3/0-500
(a)
500 N/A 3/0-500
(a)
500 N/A 3/0-500
(a)
2 380 N/A #4-500 250 N/A #6-350
300
350
N/A 3/0-500
(a)
300
350
N/A 3/0-500
(a)
380
1 380 #4-500 #4-500 250 #6-350 #6-350 300 3/0-500
(a)
3/0-500
(a)
300 3/0-500
(a)
3/0-500
(a)
2 175 #14-2/0 #14-2/0 250 #6-350 #6-350
200
225
#6-350 #6-350
200
225
#6-350 #6-350
460
1 380 #4-500 #4-500 250 #6-350 #6-350 250 #6-350 #6-350 250 #6-350 #6-350
2 175 #14-2/0 #14-2/0
100
250
#10-1/0
#6-350
#10-1/0
#6-350
150
175
#6-350 #6-350
150
175
#6-350 #6-350
575
1 380 #4-500 #4-500 250 #6-350 #6-350 200 #6-350 #6-350 N/A N/A N/A
2 175 #14-2/0 #14-2/0 100 #10-1/0 #10-1/0
125
150
#6-350 #6-350 N/A N/A N/A
Notes:
1. Optional non-fused disconnect and circuit breaker.
2. Copper wire only, based on nameplate minimum circuit ampacity (MCA).
3. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.
4. Circuit two information is the same as circuit one unless listed on a separate line below circuit one values.
5. XL - across-the-line starter and YD - wye-delta starter.
(a) Will accept 2 conduits per phase in this size.
Table 79. CustomerWire Selection - RTWD - 60 Hz - standard efficiency - standard condensing temperature (continued)
Size
Rated
Voltage
#
Conn
Wire Selection
Main Terminal Block Disconnect Circuit Breaker Hi-Fault Panel Ckt Brkr
Size Wire Range Size Wire Range Size Wire Range Size Wire Range
Amp XL YD Amp XL YD Amp XL YD Amp XL YD
Table 80. Customer Wire Selection - RTWD - 60 Hz - high efficiency - standard condensing temperature
Size
Rated
Voltage
#
Conn
Wire Selection
Main Terminal Block Disconnect Circuit Breaker Hi-Fault Panel Ckt Brkr
Size Wire Range Size Wire Range Size Wire Range Size Wire Range
Amp XL YD Amp XL YD Amp XL YD Amp XL YD
80
200
1 380 N/A #4-500 250 N/A #6-350 300 N/A 3/0-500
(a)
300 N/A 3/0-500
(a)
2 175 N/A #14-2/0 250 N/A #6-350 200 N/A #6-350 200 N/A #6-350
230
1 380 N/A #4-500 250 N/A #6-350 250 N/A #6-350 250 N/A #6-350
2 175 N/A #14-2/0 100 N/A #10-1/0 175 N/A #6-350 175 N/A #6-350
380
1 380 #4-500 #4-500 250 #6-350 #6-350 150 #6-350 #6-350 150 #6-350 #6-350
2 175 #14-2/0 #14-2/0 100 #10-1/0 #10-1/0 110 #6-350 #6-350 110 #6-350 #6-350
460
1 380 #4-500 #4-500 100 #10-1/0 #10-1/0 125 #6-350 #6-350 125 #6-350 #6-350
2 175 #14-2/0 #14-2/0 100 #10-1/0 #10-1/0 90 #6-350 #6-350 90 #6-350 #6-350
575
1 380 #4-500 #4-500 100 #10-1/0 #10-1/0 100 #6-350 #6-350 N/A N/A N/A
2 175 #14-2/0 #14-2/0 100 #10-1/0 #10-1/0 70 #6-350 #6-350 N/A N/A N/A