Installation and Maintenance Manual
Table Of Contents
- Warnings, Cautions and Notices
- Model Number Description
- General Information
- Pre-Installation
- Unit Dimensions/Weights
- Installation - Mechanical
- Location Requirements
- Rigging
- Evaporator Piping
- Condenser Water Piping (RTWD Units Only)
- Refrigerant Relief Valve Venting
- RTUD Installation
- System Configuration
- Equivalent Line Length
- Liquid Line Sizing
- Discharge (Hot Gas) Line Sizing
- Example
- Refrigerant Charge Determination
- RTUD Chilled Water Flow Control
- Oil Charge Determination
- Outdoor Air Temperature Sensor Installation Requirements
- Fan Control for the Remote Air Cooled Condenser
- RTUD Condenser Elevation Setting
- Shipping Spacers
- Installation - Electrical
- RTWD/RTUD Operating Principles
- Controls Interface
- Pre-Start Checkout
- Unit Start-Up Procedures
- Unit Shutdown
- Service and Maintenance
- Diagnostics
- Wiring Schematics

Installation - Electrical
RLC-SVX09H-EN 85
Table 77. Electrical Data - RTWD - 50 Hz - premium efficiency - standard condensing temperature
Unit
Size
Rated
Voltage
Unit Wiring
Single Point Power -
1 Power Connection
Dual Point Power -
2 Power Connections Motor Data
MCA MOP MCA MOP RLA LRA YD LRA XL
160 400/50/3 221 300 124/122 200/200 97/97 259/259 796/796
180 400/50/3 246 350 124/147 200/250 97/117 259/291 796/896
200 400/50/3 266 350 149/147 250/250 117/117 291/291 896/896
Notes:
1. Voltage Utilization Range: +/- 10% of rated voltage. Rated voltage (use range): 400/50/3 (360-440)
2. MCA–minimum circuit ampacity
3. MOP–maximum overcurrent protection
4. RLA–rated load amps are rated in accordance with UL Standard 1995.
5. LRA–locked rotor amps are based on full winding starts.
6. LRA YD–Locked Rotor Amps in Wye configuration. LRA XL–Locked Rotor Amps in the Delta configuration.
7. Local codes may take precedence.
8. Data containing information on two circuits shown as follows: circuit 1/circuit 2.
9. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) or below.
Table 78. Electrical Data - RTWD - 50 Hz - premium efficiency - high condensing temperature
Unit
Size
Rated
Voltage
Unit Wiring
Single Point Power -
1 Power Connection
Dual Point Power -
2 Power Connections Motor Data
MCA MOP MCA MOP RLA LRA YD LRA XL
160 400/50/3 268 350 150/148 250/250 118/118 259/259 796/796
180 400/50/3 297 400 150/177 250/300 118/141 259/291 796/896
200 400/50/3 320 450 179/177 300/300 141/141 291/291 896/896
Notes:
1. MCA–minimum circuit ampacity
2. MOP–maximum overcurrent protection
3. RLA–rated load amps are rated in accordance with UL Standard 1995.
4. LRA–locked rotor amps are based on full winding starts.
5. LRA YD–Locked Rotor Amps in Wye configuration. LRA XL–Locked Rotor Amps in the Delta configuration.
6. Local codes may take precedence.
7. Data containing information on two circuits shown as follows: circuit 1/circuit 2.
8. High condensing temperature option refers to entering condenser water temperatures above 95°F (35°C).
Table 79. Customer Wire Selection - RTWD - 60 Hz - standard efficiency - standard condensing temperature
Size
Rated
Voltage
#
Conn
Wire Selection
Main Terminal Block Disconnect Circuit Breaker Hi-Fault Panel Ckt Brkr
Size Wire Range Size Wire Range Size Wire Range Size Wire Range
Amp XL YD Amp XL YD Amp XL YD Amp XL YD
80
200
1 380 N/A #4-500 250 N/A #6-350 300 N/A 3/0-500
(a)
300 N/A 3/0-500
(a)
2 175 N/A #14-2/0 250 N/A #6-350 200 N/A #6-350 200 N/A #6-350
230
1 380 N/A #4-500 250 N/A #6-350 250 N/A #6-350 250 N/A #6-350
2 175 N/A #14-2/0 100 N/A #10–1/0 175 N/A #6-350 175 N/A #6-350
380
1 380 #4-500 #4-500 250 #6-350 #6-350 150 #6-350 #6-350 150 #6-350 #6-350
2 175 #14-2/0 #14-2/0 100 #10-1/0 #10-1/0 110 #6-350 #6-350 110 #6-350 #6-350
460
1 380 #4-500 #4-500 100 #10-1/0 #10-1/0 125 #6-350 #6-350 125 #6-350 #6-350
2 175 #14-2/0 #14-2/0 100 #10-1/0 #10-1/0 90 #6-350 #6-350 90 #6-350 #6-350
575
1 380 #4-500 #4-500 100 #10-1/0 #10-1/0 100 #6-350 #6-350 N/A N/A N/A
2 175 #14-2/0 #14-2/0 100 #10-1/0 #10-1/0 70 #6-350 #6-350 N/A N/A N/A