Installation - Mechanical
54 RLC-SVX09H-EN
Figure 32. Condenser pressure drop curves - RTWD 50 Hz
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
100.0 300.0 500.0 700.0 900.0 1100.0
Pressure Drop (ft. H2O)
Water Flow (GPM)
Waterside Pressure Drop - 50 Hz Units - Condenser
RTWD130 High
RTWD140 High
RTWD160 High
RTWD180 High
RTWD200 High
RTWD220 High
RTWD250 High
RTWD160 Prem
RTWD180 Prem
RTWD200 Prem