Installation and Maintenance Manual

Table Of Contents
Unit Dimensions/Weights
RLC-SVX09H-EN 21
Table 11. RTWD/RTUD 60 Hz dimensions 150-250 tons
RTWD
RTUD
High Efficiency Prem Efficiency
150-200
inch (mm)
220, 250
inch (mm)
150-200
inch (mm)
150
inch (mm)
160-200
inch (mm)
220,250
inch (mm)
A (2 pass evap)
132.3 (3360) 136.1 (3456) 147.9 (3755) 126.9 (3225) 132.3 (3360) 132.3 (3360)
B (3 pass evap)
132.8 (3371) 136.1 (3456) 150.9 (3831) 130.8 (3321) 132.8 (3371) 132.9 (3376)
C
75.6 (1920) 76.9 (1955) 76.8 (1950) 76.9 (1955) 75.6 (1920) 76.7 (1949)
D
47.3 (1202) 47.8 (1213) 47.3 (1202) 37.9 (962) 47.4 (1203) 47.4 (1203)
E
24.6 (624) 24.8 (630) 24.6 (624) 23.5 (599) 24.5 (624) 24.6 (624)
F
11.1 (282) 11.2 (295) 11.1 (282) - - -
G
32.7 (830) 33.1 (840) 33.8 (860) - - -
H
42.4 (1078) 43.9 (1115) 43.6 (1108) - - -
J (2 pass evap)
10.1 (256) 10.6 (270) 10.6 (270) 10.2/259 10.1 (256) 11.3 (263)
J (3 pass evap)
9.5 (241) 9.7 (247) 9.7 (247) 9.8/247 9.5 (241) 8.8 (223)
K (2 pass evap)
19.3 (490) 20.6 (524) 20.6 (524) 18.9/479 19.3 (490) 19.9 (483)
L (3 pass evap)
19.9 (505) 21.6 (549) 21.6 (549) 19.8/501 19.9 (505) 20.7 (526)
M
36.0 (914) 36.0 (914) 36.0 (914) 36.0 (914) 36.0 (914) 36.0 (914)
N
36.0 (914) 36.0 (914) 36.0 (914) 36.0 (914) 36.0 (914) 36.0 (914)
P*
40 (1016)* 40 (1016)* 40 (1016)* 40 (1016)* 40 (1016)* 40 (1016)*
R
114.8 (2916) 114.8 (2916) 134.5 (3416) 114.8 (2916) 114.8 (2916) 114.8 (2916)
S
36.0 (914) 36.0 (914) 36.0 (914) 36.0 (914) 36.0 (914) 36.0 (914)
Reference
1
Evaporator Water Inlet
2
Evaporator Water Outlet
3
Condenser Water Inlet (RTWD only)
4
Condenser Water Outlet (RTWD only)
5
Power Disconnect
6
Power Wire
7
Control Wire
8
Control Panel
9
Condenser Return Waterbox End (RTWD only) - minimum clearance (for tube removal)
10
Condenser Supply Waterbox End (RTWD only) - minimum clearance (for maintenance)
11
Condenser (RTWD only)
12
Evaporator
13
Panel Power Section - door swing 31.3 inch (796.9 mm)
14
Panel Power Section - door swing 31.1 inch (790.1 mm)
15
Panel Control Section - door swing 22.4 inch (568.14 mm)
*
Control panel clearance is 36 or 40 inch (914 or 1016 mm) depending on voltages, starter type, unit application
and local code; 42 inch (1067 mm) clearance required to other grounded parts; two units with panels facing
each other or other live parts require a clearance of 48 inch (1220 mm).
**
Sound attenuator may increase the footprint - submittal should be used.