Installation and Maintenance Manual

Table Of Contents
Installation - Electrical
104 RLC-SVX09H-EN
Table 87. Customer Wire Selection - RTWD - 50 Hz - high efficiency - high condensing temperature
Size
Rated
Voltage
#
Conn
Wire Selection
Main Terminal Block Disconnect Circuit Breaker Hi-Fault Panel Ckt Brkr
Size Wire Range Size Wire Range Size Wire Range Size Wire Range
Amp XL YD Amp XL YD Amp XL YD Amp XL YD
60 400
1 380 #4–500 #4–500 250 #6–#350 #6–#350 150 #6–#350 #6–#350 150 #6–#350 #6–#350
2 175 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0
110
100
#6–#350 #6–#350
110
100
#6–#350 #6–#350
70 400
1 380 #4–500 #4–500 250 #6–#350 #6–#350 175 #6–#350 #6–#350 175 #6–#350 #6–#350
2 175 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0 125 #6–#350 #6–#350 125 #6–#350 #6–#350
80 400
1 380 #4–500 #4–500 250 #6–#350 #6–#350 225 #6–#350 #6–#350 225 #6–#350 #6–#350
2 175 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0
125
150
#6–#350 #6–#350
125
150
#6–#350 #6–#350
90 400
1 380 #4–500 #4–500 250 #6–#350 #6–#350 225 #6–#350 #6–#350 225 #6–#350 #6–#350
2 175 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0 150 #6–#350 #6–#350 150 #6–#350 #6–#350
100 400
1 380 #4–500 #4–500 250 #6–#350 #6–#350 250 #6–#350 #6–#350 250 #6–#350 #6–#350
2 175 #14–2/0 #14–2/0
100
250
#10–1/0
#6–#350
#10–1/0
#6–#350
150
175
#6–#350 #6–#350
150
175
#6–#350 #6–#350
110 400
1 380 #4–500 #4–500 250 #6–#350 #6–#350 250 3/0-500
(a)
3/0-500
(a)
250 3/0-500
(a)
3/0-500
(a)
2 175 #14–2/0 #14–2/0 250 #6–#350 #6–#350
200
175
#6–#350 #6–#350
200
175
#6–#350 #6–#350
120 400
1 380 #4–500 #4–500 250 #6–#350 #6–#350 300 3/0-500
(a)
3/0-500
(a)
300 3/0-500
(a)
3/0-500
(a)
2 175 #14–2/0 #14–2/0 250 #6–#350 #6–#350
200
225
#6–#350 #6–#350
200
225
#6–#350 #6–#350
130 400
1 380 #4–500 #4–500 250 #6-350 #6–#350 300 3/0-500
(a)
3/0-500
(a)
300 3/0-500
(a)
3/0-500
(a)
2 175 #14-2/0 #14-2/0 250 #6-350 #6-350
225
200
#6-350 #6-350
225
200
#6-350 #6-350
140 400
1 380 #4–500 #4–500 400 3/0-500
(a)
3/0-500
(a)
350 3/0-500
(a)
3/0-500
(a)
350 3/0-500
(a)
3/0-500
(a)
2
XL 175/
380
YD 175
#14-2/0
#4–500
#14-2/0 250 #6-350 #6-350
225
250
#6-350 #6-350
225
250
#6-350 #6-350
160 400
1 380 #4–500 #4–500 400 3/0-500
(a)
3/0-500
(a)
350 3/0-500
(a)
3/0-500
(a)
350 3/0-500
(a)
3/0-500
(a)
2
XL 380
YD 175
#4–500 #14-2/0 250 #6-350 #6-350 250 #6-350 #6-350 250 #6-350 #6-350
180 400
1 380 #4–500 #4–500 400 3/0-500
(a)
3/0-500
(a)
400 3/0-500
(a)
3/0-500
(a)
400 3/0-500
(a)
3/0-500
(a)
2
XL 380
YD
175/
380
#4–500
#14-2/0
#4–500
250 #6-350 #6-350
250
300
#6-350
3/0-500
(a)
#6-350
3/0-500
(a)
250
300
#6-350
3/0-500
(a)
#6-350
3/0-500
(a)
200 400
1 380 #4–500 #4–500 400 3/0-500
(a)
3/0-500
(a)
450 3/0-500
(a)
3/0-500
(a)
450 3/0-500
(a)
3/0-500
(a)
2 380 #4–500 #4–500 250 #6-350 #6-350 300 3/0-500
(a)
3/0-500
(a)
300 3/0-500
(a)
3/0-500
(a)
220 400
1 380 #4–500 #4–500 400 3/0-500
(a)
3/0-500
(a)
500 3/0-500
(a)
3/0-500
(a)
500 3/0-500
(a)
3/0-500
(a)
2 380 #4–500 #4–500 250 #6-350 #6-350
300
350
3/0-500
(a)
3/0-500
(a)
300
350
3/0-500
(a)
3/0-500
(a)
250 400
1 380 #4–500 #4–500 600 3/0-500
(a)
3/0-500
(a)
500 3/0-500
(a)
3/0-500
(a)
500 3/0-500
(a)
3/0-500
(a)
2 380 #4–500 #4–500 250 #6-350 #6-350 350 3/0-500
(a)
3/0-500
(a)
350 3/0-500
(a)
3/0-500
(a)
Notes:
1. Optional non-fused disconnect and circuit breaker.
2. Copper wire only, based on nameplate minimum circuit ampacity (MCA).
3. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.
4. Circuit two information is the same as circuit one unless listed on a separate line below circuit one values.
5. XL - across-the-line starter and YD - wye-delta starter.
(a) Will accept 2conduits per phase in this size.