Installation and Maintenance Manual
Table Of Contents
- Warnings, Cautions and Notices
- Model Number Description
- General Information
- Pre-Installation
- Unit Dimensions/Weights
- Installation - Mechanical
- Location Requirements
- Rigging
- Evaporator Piping
- Condenser Water Piping (RTWD Units Only)
- Refrigerant Relief Valve Venting
- RTUD Installation
- System Configuration
- Equivalent Line Length
- Liquid Line Sizing
- Discharge (Hot Gas) Line Sizing
- Example
- Refrigerant Charge Determination
- RTUD Chilled Water Flow Control
- Oil Charge Determination
- Outdoor Air Temperature Sensor Installation Requirements
- Fan Control for the Remote Air Cooled Condenser
- RTUD Condenser Elevation Setting
- Shipping Spacers
- Installation - Electrical
- RTWD/RTUD Operating Principles
- Controls Interface
- Pre-Start Checkout
- Unit Start-Up Procedures
- Unit Shutdown
- Service and Maintenance
- Diagnostics
- Wiring Schematics

Installation - Electrical
RLC-SVX09H-EN 101
250
200
1 760 N/A #4-500
(a)
800 N/A #1-500
(b)
1000 N/A 250-500
(c)
1000 N/A 250-500
(c)
2 760 N/A #4-500
(a)
600 N/A 3/0-500
(a)
700 N/A #1-500
(b)
700 N/A #1-500
(b)
230
1 760 N/A #4-500
(a)
800 N/A #1-500
(b)
1000 N/A 250-500
(c)
1000 N/A 250-500
(c)
2 760 N/A #4-500
(a)
600 N/A 3/0-500
(a)
700 N/A #1-500
(b)
700 N/A #1-500
(b)
380
1 760
#4-
500
(a)
#4-500
(a)
600 3/0-500
(a)
3/0-500
(a)
600 3/0-500
(a)
3/0-500
(a)
600 3/0-500
(a)
3/0-500
(a)
2 380 #4-500 #4-500 250 #6-350 #6-350 450 3/0-500
(a)
3/0-500
(a)
450 3/0-500
(a)
3/0-500
(a)
460
1 380 #4-500 #4-500 600 3/0-500
(a)
3/0-500
(a)
500 3/0-500
(a)
3/0-500
(a)
500 3/0-500
(a)
3/0-500
(a)
2 380 #4-500 #4-500 250 #6-350 #6-350 350 3/0-500
(a)
3/0-500
(a)
350 3/0-500
(a)
3/0-500
(a)
575
1 380 #4-500 #4-500 400 3/0-500
(a)
3/0-500
(a)
400 3/0-500
(a)
3/0-500
(a)
N/A N/A N/A
2 175 #14-2/0 #14-2/0 250 #6-350 #6-350 250 #6-350 #6-350 N/A N/A N/A
Notes:
1. Optional non-fused disconnect and circuit breaker.
2. Copper wire only, based on nameplate minimum circuit ampacity (MCA).
3. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.
4. Circuit two information is the same as circuit one unless listed on a separate line below circuit one values.
5. XL - across-the-line starter and YD - wye-delta starter.
(a) Will accept 2 conduits per phase in this size.
(b) Will accept 3 conduits per phase in this size.
(c) Will accept 4 conduits per phase in this size.
(d) Will accept 4 conduits per phase in this size.
Table 84. Customer Wire Selection - RTUD - 60 Hz (continued)
Size
Rated
Voltage
#
Conn
Wire Selection
Main Terminal Block Disconnect Circuit Breaker Hi-Fault Panel Ckt Brkr
Size Wire Range Size Wire Range Size Wire Range Size Wire Range
Amp XL YD Amp XL YD Amp XL YD Amp XL YD