Catalogue
RLC-PRC029-EN 95
Electrical Data
RTWD
180
200/60/3 1 760 N/A (2)#4–500 600 N/A 3/0-(2)500 700 N/A #1-(3)500
200/60/3 2 380 N/A #4–500
250
400
N/A
#6-350
3/0-(2)500
400
500
N/A 3/0-(2)500
230/60/3 1 760 N/A (2)#4–500 600 N/A 3/0-(2)500 600 N/A 3/0-(2)500
230/60/3 2 380 N/A #4–500 250 N/A #6-350
350
400
N/A 3/0-(2)500
380/60/3 1 380 #4–500 #4–500 400 3/0-(2)500 3/0-(2)500 350 3/0-(2)500 3/0-(2)500
380/60/3 2
XL 175/308
YD 175
#14-2/0
#4–500
#4–500 250 #6-350 #6-350
225
250
#6-350 #6-350
460/60/3 1 380 #4–500 #4–500 250 #6-350 #6-350 300 3/0-(2)500 3/0-(2)500
460/60/3 2 175 #14-2/0 #14-2/0
100
250
1/0-#10
#6-350
1/0-#10
#6-350
175
225
#6-350 #6-350
575/60/3 1 175 #14-2/0 #14-2/0 250 #6-350 #6-350 250 #6-350 #6-350
575/60/3 2 175 #14-2/0 #14-2/0 100 1/0-#10 1/0-#10
150
175
#6-350 #6-350
RTWD
200
200/60/3 1 760 N/A (2)#4–500 600 N/A 3/0-(2)500 700 N/A #1-(3)500
200/60/3 2 380 N/A #4–500 400 N/A 3/0-(2)500 500 N/A 3/0-(2)500
230/60/3 1 760 N/A (2)#4–500 600 N/A 3/0-(2)500 600 N/A 3/0-(2)500
230/60/3 2 380 N/A #4–500 250 N/A #6-350 400 N/A 3/0-(2)500
380/60/3 1 380 #4–500 #4–500 400 3/0-(2)500 3/0-(2)500 350 3/0-(2)500 3/0-(2)500
380/60/3 2
XL 380
YD 175
#4–500 #14-2/0 250 #6-350 #6-350 250 #6-350 #6-350
460/60/3 1 380 #4–500 #4–500 250 #6-350 #6-350 300 3/0-(2)500 3/0-(2)500
460/60/3 2 175 #14-2/0 #14-2/0 250 #6-350 #6-350 225 #6-350 #6-350
575/60/3 1 380 #4–500 #4–500 250 #6-350 #6-350 250 3/0-(2)500 3/0-(2)500
575/60/3 2 175 #14-2/0 #14-2/0 100 1/0-#10 1/0-#10 175 #6-350 #6-350
1. Optional non-fused disconnect and circuit breaker.
2. Copper wire only, based on nameplate minimum circuit ampacity (MCA).
3. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.
4. Circuit two information is the same as circuit one unless listed on a separate line below circuit one values.
5. XL - across-the-line starter and YD - wye-delta starter.
Table 50. Customer Wire Selection – RTWD – 60 Hz – premium efficiency – standard condensing temperature
Wire Selection
Main Terminal Block
Wire Selection
Non-Fused Disconnect
Wire Selection
Circuit Breaker
Unit
ID
Rated
Voltage
#
Conn
Size
amps
XL Wire
Range
YD Wire
Range
Size
amps
XL Wire
Range
YD Wire
Range
Size
amps
XL Wire
Range
YD Wire
Range