Catalogue

RLC-PRC029-EN 85
Electrical Data
Table 45. Electrical Data – RTWD – 50 Hz – high efficiency – high condensing temperature
Unit Wiring Motor Data
Unit ID Rated Voltage
# Power
Conns
MCA
Ckt 1/Ckt 2
MOP
Ckt 1/Ckt 2
RLA
Ckt 1/Ckt 2
LRA YD
Ckt 1/Ckt 2
LRA XL
Ckt 1/Ckt 2
RTWD 60
400/50/3 1 110 150
48/48 112/112 370/370
400/50/3 2 62/60 110/100
RTWD 70
400/50/3 1 133 175
58/58 129/129 427/427
400/50/3 2 75/73 125/125
RTWD 80
400/50/3 1 153 225
58/74 129/144 427/462
400/50/3 2 75/93 125/150
RTWD 90
400/50/3 1 169 225
74/74 144/144 462/462
400/50/3 2 95/93 150/150
RTWD 100
400/50/3 1 186 250
74/88 144/180 462/589
400/50/3 2 95/110 150/175
RTWD 110
400/50/3 1 200 250
88/88 180/180 589/589
400/50/3 2 112/110 200/175
RTWD 120
400/50/3 1 215 300
88/100 180/217 589/668
400/50/3 2 112/125 200/225
RTWD 130
400/50/3 1 226 300
100/98 217/217 668/668
400/50/3 2 128/123 225/200
RTWD 140
400/50/3 1 250 350
100/118 217/259 668/796
400/50/3 2 128/148 225/250
RTWD 160
400/50/3 1 268 350
118/118 259/259 796/796
400/50/3 2 150/148 250/250
RTWD 180
400/50/3 1 297 400
118/141 259/291 796/896
400/50/3 2 150/177 250/300
RTWD 200
400/50/3 1 320 450
141/141 291/291 896/896
400/50/3 2 179/177 300/300
RTWD 220
400/50/3 1 352 500
141/167 291/354 896/1089
400/50/3 2 179/209 300/350
RTWD 250
400/50/3 1 378 500
167/167 354/354 1089/1089
400/50/3 2 211/209 350/350
1. MCA–minimum circuit ampacity
2. MOP–maximum overcurrent protection
3. RLA–rated load amps are rated in accordance with UL Standard 1995.
4. LRA–locked rotor amps are based on full winding starts.
5. LRA YD–Locked Rotor Amps in Wye configuration. LRA XL–Locked Rotor Amps in the Delta configuration.
6. Local codes may take precedence.
7. Data containing information on two circuits shown as follows: circuit 1/circuit 2.
8. High condensing temperature option refers to entering condenser water temperatures above 95°F (35°C).