Catalogue

84 RLC-PRC029-EN
Electrical Data
Table 44. Electrical Data – RTWD – 50 Hz – high efficiency – standard condensing temperature
Unit Wiring Motor Data
Unit ID Rated Voltage
# Power
Conns
MCA
Ckt 1/Ckt 2
MOP
Ckt 1/Ckt 2
RLA
Ckt 1/Ckt 2
LRA YD
Ckt 1/Ckt 2
LRA XL
Ckt 1/Ckt 2
RTWD 60
400/50/3 1 88 125
38/38 112/112 370/370
400/50/3 2 50/48 80/80
RTWD 70
400/50/3 1 103 125
45/45 129/129 427/427
400/50/3 2 58/56 100/100
RTWD 80
400/50/3 1 121 175
45/59 129/144 427/462
400/50/3 2 58/74 100/125
RTWD 90
400/50/3 1 135 175
59/59 144/144 462/462
400/50/3 2 76/74 125/125
RTWD 100
400/50/3 1 150 200
59/71 144/180 462/589
400/50/3 2 76/89 125/150
RTWD 110
400/50/3 1 162 225
71/71 180/180 589/589
400/50/3 2 91/89 150/150
RTWD 120
400/50/3 1 178 250
71/84 180/217 589/668
400/50/3 2 91/105 150/175
RTWD 130
400/50/3 1 192 250
84/84 217/217 668/668
400/50/3 2 108/105 175/175
RTWD 140
400/50/3 1 209 300
84/98 217/259 668/796
400/50/3 2 108/123 175/200
RTWD 160
400/50/3 1 223 300
98/98 259/259 796/796
400/50/3 2 125/123 200/200
RTWD 180
400/50/3 1 247 350
98/117 259/291 796/896
400/50/3 2 125/147 200/250
RTWD 200
400/50/3 1 266 350
117/117 291/291 896/896
400/50/3 2 149/147 250/250
RTWD 220
400/50/3 1 296 400
117/141 291/354 896/1089
400/50/3 2 149/177 250/300
RTWD 250
400/50/3 1 320 450
141/141 354/354 1089/1089
400/50/3 2 179/177 300/300
1. MCA–minimum circuit ampacity
2. MOP–maximum overcurrent protection
3. RLA–rated load amps are rated in accordance with UL Standard 1995.
4. LRA–locked rotor amps are based on full winding starts.
5. LRA YD–Locked Rotor Amps in Wye configuration. LRA XL–Locked Rotor Amps in the Delta configuration.
6. Local codes may take precedence.
7. Data containing information on two circuits shown as follows: circuit 1/circuit 2.
8. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.