Catalogue

RLC-PRC029-EN 83
Electrical Data
Table 43. Electrical Data – RTWD – 50 Hz – standard efficiency – standard condensing temperature
Unit Wiring Motor Data
Unit ID Rated Voltage
# Power
Conns
MCA
Ckt 1/Ckt 2
MOP
Ckt 1/Ckt 2
RLA
Ckt 1/Ckt 2
LRA YD
Ckt 1/Ckt 2
LRA XL
Ckt 1/Ckt 2
RTWD 70
400/50/3 1 106 150
46/46 129/129 427/427
400/50/3 2 60/58 100/100
RTWD 80
400/50/3 1 123 175
46/60 129/144 427/462
400/50/3 2 60/75 100/125
RTWD 90
400/50/3 1 137 175
60/60 144/144 462/462
400/50/3 2 77/75 125/125
RTWD 100
400/50/3 1 152 200
60/72 144/180 462/589
400/50/3 2 77/90 125/150
RTWD 110
400/50/3 1 164 225
72/72 180/180 589/589
400/50/3 2 92/90 150/150
RTWD 120
400/50/3 1 180 250
72/85 180/217 589/668
400/50/3 2 92/106 150/175
RTWD 130
400/50/3 1 193 250
85/85 217/217 668/668
400/50/3 2 108/106 175/175
RTWD 140
400/50/3 1 211 300
85/99 217/259 668/796
400/50/3 2 108/124 175/200
RTWD 150
400/50/3 1 225 300
99/99 259/259 796/796
400/50/3 2 126/124 200/200
1. MCA–minimum circuit ampacity
2. MOP–maximum overcurrent protection
3. RLA–rated load amps are rated in accordance with UL Standard 1995.
4. LRA–locked rotor amps are based on full winding starts.
5. LRA YD–Locked Rotor Amps in Wye configuration. LRA XL–Locked Rotor Amps in the Delta configuration.
6. Local codes may take precedence.
7. Data containing information on two circuits shown as follows: circuit 1/circuit 2.
8. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.