Catalogue

82 RLC-PRC029-EN
Electrical Data
RTUD 150
208-230/60/3 Standard 6 37.5 40
208-230/60/3 Low 6 37.5 40
460/60/3 Standard 3 18.8 20
460/60/3 Low 3 18.8 20
575/60/3 Standard 2.5 15.6 15
575/60/3 Low 2.5 16.8 15
RTUD 160
208-230/60/3 Standard 6 37.5 40
208-230/60/3 Low 6 37.5 40
460/60/3 Standard 3 18.8 20
460/60/3 Low 3 18.8 20
575/60/3 Standard 2.5 15.6 15
575/60/3 Low 2.5 16.8 15
RTUD 180
208-230/60/3 Standard 6 37.5/49.5 40/50
208-230/60/3 Low 6 37.5/49.5 40/50
460/60/3 Standard 3 18.8/24.8 20/25
460/60/3 Low 3 18.8/24.8 20/25
575/60/3 Standard 2.5 15.6/20.6 15/20
575/60/3 Low 2.5 16.8/21.8 15/20
RTUD 200
208-230/60/3 Standard 6 49.5 50
208-230/60/3 Low 6 49.5 50
460/60/3 Standard 3 24.8 25
460/60/3 Low 3 24.8 25
575/60/3 Standard 2.5 20.6 20
575/60/3 Low 2.5 21.8 20
RTUD 220
208-230/60/3 Standard 6 49.5 50
208-230/60/3 Low 6 49.5 50
460/60/3 Standard 3 24.8 25
460/60/3 Low 3 24.8 25
575/60/3 Standard 2.5 20.6 20
575/60/3 Low 2.5 21.8 20
RTUD 2500
208-230/60/3 Standard 6 49.5 50
208-230/60/3 Low 6 49.5 50
460/60/3 Standard 3 24.8 25
460/60/3 Low 3 24.8 25
575/60/3 Standard 2.5 20.6 20
575/60/3 Low 2.5 21.8 20
1. MCA–minimum circuit ampacity
2. MOP–maximum overcurrent protection
3. FLA–fan rated load amps
4. Local codes may take precedence.
5. Information is the same for both circuits unless it is shown as: circuit 1/circuit 2.
Table 42. Electrical Data – Trane Air-Cooled Condenser – 60 Hz
Unit Wiring
Unit ID Rated Voltage Ambient Fan FLA Fan MCA Fan MOP