RLC-PRC029-EN 81
Electrical Data
Table 42. Electrical Data – Trane Air-Cooled Condenser – 60 Hz
Unit Wiring
Unit ID Rated Voltage Ambient Fan FLA Fan MCA Fan MOP
RTUD 80
208-230/60/3 Standard 6 37.5 40
208-230/60/3 Low 6 37.5 40
460/60/3 Standard 3 18.8 20
460/60/3 Low 3 18.8 20
575/60/3 Standard 2.5 15.6 15
575/60/3 Low 2.5 16.8 15
RTUD 90
208-230/60/3 Standard 6 49.5 50
208-230/60/3 Low 6 49.5 50
460/60/3 Standard 3 24.8 25
460/60/3 Low 3 24.8 25
575/60/3 Standard 2.5 20.6 20
575/60/3 Low 2.5 21.8 20
RTUD 100
208-230/60/3 Standard 6 49.5 50
208-230/60/3 Low 6 49.5 50
460/60/3 Standard 3 24.8 25
460/60/3 Low 3 24.8 25
575/60/3 Standard 2.5 20.6 20
575/60/3 Low 2.5 21.8 20
RTUD 110
208-230/60/3 Standard 6 49.5 50
208-230/60/3 Low 6 49.5 50
460/60/3 Standard 3 24.8 25
460/60/3 Low 3 24.8 25
575/60/3 Standard 2.5 20.6 20
575/60/3 Low 2.5 21.8 20
RTUD 120
208-230/60/3 Standard 6 61.5 60
208-230/60/3 Low 6 61.5 60
460/60/3 Standard 3 30.8 30
460/60/3 Low 3 30.8 30
575/60/3 Standard 2.5 18.8 25
575/60/3 Low 2.5 24.8 25
RTUD 130
208-230/60/3 Standard 6 61.5 60
208-230/60/3 Low 6 61.5 60
460/60/3 Standard 3 30.8 30
460/60/3 Low 3 30.8 30
575/60/3 Standard 2.5 18.8 25