Catalogue

80 RLC-PRC029-EN
Electrical Data
200/60/3 1 725 1000
320/320 600/600 1845/1845
200/60/3 2 405/400 700/700
230/60/3 1 630 800
278/278 506/506 1556/1556
230/60/3 2 352/345 600/600
RTUD 200
380/60/3 1 381 500
168/168 316/316 973/973
380/60/3 2 213/210 350/350
460/60/3 1 297 400
131/131 252/252 774/774
460/60/3 2 166/164 250/250
575/60/3 1 252 350
111/111 205/205 631/631
575/60/3 2 141/139 250/225
200/60/3 1 743 1000
320/335 600/701 1845/2156
200/60/3 2 405/419 700/700
230/60/3 1 701 1000
278/335 506/571 1556/1756
230/60/3 2 352/419 600/700
RTUD 220
380/60/3 1 424 600
168/203 316/345 973/1060
380/60/3 2 213/254 350/450
460/60/3 1 343 500
131/168 252/285 774/878
460/60/3 2 166/210 250/350
575/60/3 1 277 400
111/131 205/229 631/705
575/60/3 2 141/164 250/250
200/60/3 1 758 1000
335/335 701/701 2156/2156
200/60/3 2 423/419 700/700
230/60/3 1 758 1000
335/335 571/571 1756/1756
230/60/3 2 423/419 700/700
RTUD 250
380/60/3 1 459 600
203/203 345/345 1060/1060
380/60/3 2 256/254 450/450
460/60/3 1 380 500
168/168 285/285 878/878
460/60/3 2 212/210 350/350
575/60/3 1 297 400
131/131 229/229 705/705
575/60/3 2 166/164 250/250
1. MCA–minimum circuit ampacity
2. MOP–maximum overcurrent protection
3. RLA–rated load amps are rated in accordance with UL Standard 1995.
4. LRA–locked rotor amps are based on full winding starts.
5. LRA YD–Locked Rotor Amps in Wye configuration. LRA XL–Locked Rotor Amps in the Delta configuration.
6. Local codes may take precedence.
7. Data containing information on two circuits shown as follows: circuit 1/circuit 2.
8. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.
Table 41. Electrical Data – RTUD – 60 Hz
Unit Wiring Motor Data
Unit ID Rated Voltage
# Power
Conns
MCA
Ckt 1/Ckt 2
MOP
Ckt 1/Ckt 2
RLA
Ckt 1/Ckt 2
LRA YD
Ckt 1/Ckt 2
LRA XL
Ckt 1/Ckt 2