Catalogue

76 RLC-PRC029-EN
Electrical Data
200/60/3 1 583 800
236/274 487/600 1498/1845
200/60/3 2 300/343 500/600
230/60/3 1 511 700
203/243 427/506 1314/1556
230/60/3 2 258/304 450/500
RTWD 180
380/60/3 1 307 450
124/144 260/316 801/973
380/60/3 2 158/180 250/300
460/60/3 1 253 350
102/119 212/252 652/774
460/60/3 2 130/149 225/250
575/60/3 1 207 300
84/97 172/205 528/631
575/60/3 2 107/122 175/200
RTWD 200
200/60/3 1 621 800
274/274 600/600 1845/1845
200/60/3 2 347/343 600/600
230/60/3 1 551 700
243/243 506/506 1556/1556
230/60/3 2 308/304 500/500
380/60/3 1 327 450
144/144 316/316 973/973
380/60/3 2 183/180 300/300
460/60/3 1 270 350
119/119 252/252 774/774
460/60/3 2 151/149 250/250
575/60/3 1 220 300
97/97 205/205 631/631
575/60/3 2 123/122 200/200
1. MCA–minimum circuit ampacity
2. MOP–maximum overcurrent protection
3. RLA–rated load amps are rated in accordance with UL Standard 1995.
4. LRA–locked rotor amps are based on full winding starts.
5. LRA YD–Locked Rotor Amps in Wye configuration. LRA XL–Locked Rotor Amps in the Delta configuration.
6. Local codes may take precedence.
7. Data containing information on two circuits shown as follows: circuit 1/circuit 2.
8. High condensing temperature option refers to entering condenser water temperatures above 95°F (35°C).
Table 40. Electrical Data – RTWD – 60Hz – premium efficiency – high condensing temperature
Unit Wiring Motor Data
Unit ID Rated Voltage
# Power
Conns
MCA
Ckt 1/Ckt 2
MOP
Ckt 1/Ckt 2
RLA
Ckt 1/Ckt 2
LRA YD
Ckt 1/Ckt 2
LRA XL
Ckt 1/Ckt 2