Electrical Data
200/60/3 1 639 800
282/282 600/600 1845/1845
200/60/3 2 357/353 600/600
230/60/3 1 551 700
243/243 506/506 1556/1556
230/60/3 2 308/304 500/500
RTWD 200
380/60/3 1 329 450
145/145 316/316 973/973
380/60/3 2 184/182 300/300
460/60/3 1 270 350
119/119 252/252 774/774
460/60/3 2 151/149 250/250
575/60/3 1 220 300
97/97 205/205 631/631
575/60/3 2 123/122 200/200
200/60/3 1 702 1000
282/332 600/701 1845/2156
200/60/3 2 357/415 600/700
230/60/3 1 608 800
243/289 506/571 1556/1756
230/60/3 2 308/362 500/600
RTWD 220
380/60/3 1 373 500
145/180 316/345 973/1060
380/60/3 2 184/225 300/400
460/60/3 1 303 400
119/145 252/285 774/878
460/60/3 2 151/182 250/300
575/60/3 1 244 350
97/116 205/229 631/705
575/60/3 2 123/145 200/250
RTWD 250
200/60/3 1 752 1000
332/332 701/701 2156/2156
200/60/3 2 420/415 700/700
230/60/3 1 654 800
289/289 571/571 1756/1756
230/60/3 2 365/362 600/600
380/60/3 1 408 500
180/180 345/345 1060/1060
380/60/3 2 228/225 400/400
460/60/3 1 329 450
145/145 285/285 878/878
460/60/3 2 184/182 300/300
575/60/3 1 263 350
116/116 229/229 705/705
575/60/3 2 147/145 250/250
1. MCA–minimum circuit ampacity
2. MOP–maximum overcurrent protection
3. RLA–rated load amps are rated in accordance with UL Standard 1995.
4. LRA–locked rotor amps are based on full winding starts.
5. LRA YD–Locked Rotor Amps in Wye configuration. LRA XL–Locked Rotor Amps in the Delta configuration.
6. Local codes may take precedence.
7. Data containing information on two circuits shown as follows: circuit 1/circuit 2.
8. High condensing temperature option refers to entering condenser water temperatures above 95°F (35°C).
Table 39. Electrical Data – RTWD – 60Hz – high efficiency – high condensing temperature
Unit Wiring Motor Data
Unit ID Rated Voltage
# Power
Conns
MCA
Ckt 1/Ckt 2
MOP
Ckt 1/Ckt 2
RLA
Ckt 1/Ckt 2
LRA YD
Ckt 1/Ckt 2
LRA XL
Ckt 1/Ckt 2