Catalogue
70 RLC-PRC029-EN
Electrical Data
RTWD 180
200/60/3 1 481 700
194/226 487/600 1498/1845
200/60/3 2 247/283 400/500
230/60/3 1 420 600
170/197 427/506 1314/1556
230/60/3 2 217/247 350/400
380/60/3 1 256 350
103/120 260/316 801/973
380/60/3 2 131/150 225/250
460/60/3 1 212 300
85/100 212/252 652/774
460/60/3 2 109/125 175/225
575/60/3 1 171 250
68/81 172/205 528/631
575/60/3 2 87/102 150/175
RTWD 200
200/60/3 1 513 700
226/226 600/600 1845/1845
200/60/3 2 287/283 500/500
230/60/3 1 447 600
197/197 506/506 1556/1556
230/60/3 2 250/247 400/400
380/60/3 1 273 350
120/120 316/316 973/973
380/60/3 2 153/150 250/250
460/60/3 1 227 300
100/100 252/252 774/774
460/60/3 2 127/125 225/225
575/60/3 1 184 250
81/81 205/205 631/631
575/60/3 2 103/102 175/175
1. MCA–minimum circuit ampacity
2. MOP–maximum overcurrent protection
3. RLA–rated load amps are rated in accordance with UL Standard 1995.
4. LRA–locked rotor amps are based on full winding starts.
5. LRA YD–Locked Rotor Amps in Wye configuration. LRA XL–Locked Rotor Amps in the Delta configuration.
6. Local codes may take precedence.
7. Data containing information on two circuits shown as follows: circuit 1/circuit 2.
8. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.
Table 38. Electrical Data – RTWD – 60 Hz – premium efficiency – standard condensing temperature
Unit Wiring Motor Data
Unit ID Rated Voltage
# Power
Conns
MCA
Ckt 1/Ckt 2
MOP
Ckt 1/Ckt 2
RLA
Ckt 1/Ckt 2
LRA YD
Ckt 1/Ckt 2
LRA XL
Ckt 1/Ckt 2