Catalogue
64 RLC-PRC029-EN
Electrical Data
200/60/3 1 356 500
142/168 355/419 1137/1368
200/60/3 2 182/210 300/350
230/60/3 1 309 450
123/146 294/367 942/1200
230/60/3 2 157/183 250/300
RTWD 120
380/60/3 1 187 250
75/88 177/229 566/747
380/60/3 2 96/110 150/175
460/60/3 1 155 225
62/73 147/184 471/600
460/60/3 2 79/91 125/150
575/60/3 1 125 175
50/59 118/148 377/483
575/60/3 2 64/74 110/125
200/60/3 1 382 500
168/168 419/419 1368/1368
200/60/3 2 214/210 350/350
230/60/3 1 332 450
146/146 367/367 1200/1200
230/60/3 2 186/183 300/300
RTWD 130
380/60/3 1 200 250
88/88 229/229 747/747
380/60/3 2 112/110 200/175
460/60/3 1 166 225
73/73 184/184 600/600
460/60/3 2 93/91 150/150
575/60/3 1 134 175
59/59 148/148 483/483
575/60/3 2 75/74 125/125
200/60/3 1 425 600
168/202 419/487 1368/1368
200/60/3 2 214/253 350/450
230/60/3 1 368 500
146/175 367/427 1200/1314
230/60/3 2 186/219 300/350
RTWD 140
380/60/3 1 223 300
88/106 229/260 747/801
380/60/3 2 112/133 200/225
460/60/3 1 185 250
73/88 184/212 600/652
460/60/3 2 93/110 150/175
575/60/3 1 148 200
59/70 148/172 483/528
575/60/3 2 75/88 125/150
1. MCA–minimum circuit ampacity
2. MOP–maximum overcurrent protection
3. RLA–rated load amps are rated in accordance with UL Standard 1995.
4. LRA–locked rotor amps are based on full winding starts.
5. LRA YD–Locked Rotor Amps in Wye configuration. LRA XL–Locked Rotor Amps in the Delta configuration.
6. Local codes may take precedence.
7. Data containing information on two circuits shown as follows: circuit 1/circuit 2.
8. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.
Table 36. Electrical Data – RTWD – 60 Hz – standard efficiency – standard condensing temperature
Unit Wiring Motor Data
Unit ID
Rated
Voltage
# Power
Connections
MCA
Ckt 1/Ckt 2
MOP
Ckt 1/Ckt 2
RLA
Ckt 1/Ckt 2
LRA YD
Ckt 1/Ckt 2
LRA XL
Ckt 1/Ckt 2