Catalogue
58 RLC-PRC029-EN
Performance Data
9
60
268.9 40.7 6.5 254.1 45.3 5.6 238.6 50.5 4.7
70
315.6 48.2 6.5 298.5 53.6 5.5 280.4 59.8 4.7
80
361.6 56.0 6.4 341.9 62.2 5.5 320.9 69.4 4.6
90
416.7 64.0 6.5 393.8 70.9 5.5 369.4 79.0 4.7
100
444.9 67.4 6.6 420.7 74.9 5.6 395.0 83.5 4.7
110
476.9 71.3 6.7 451.0 79.3 5.7 423.5 88.4 4.8
120
516.0 77.7 6.6 488.4 86.4 5.6 458.9 96.3 4.7
130
555.3 84.3 6.6 526.4 93.8 5.6 495.4 104.5 4.7
140
604.1 91.6 6.6 573.3 101.7 5.6 540.6 113.3 4.8
160
658.2 98.9 6.6 625.0 109.5 5.7 590.3 121.9 4.8
180
725.6 110.0 6.6 688.4 122.0 5.6 649.6 135.9 4.8
200
795.6 120.3 6.6 755.2 133.6 5.6 712.8 149.0 4.8
220
867.5 135.0 6.4 824.9 148.7 5.5 780.2 164.6 4.7
250
946.2 148.8 6.3 901.1 162.5 5.5 853.9 178.6 4.8
1. Rated in accordance with AHRI Standard 550/590, based on an evaporator temperature drop of 5.6°C, 0.054 L/s per kW on the condenser, evaporator
fouling factor of 0.01761°K·m³/kW and condenser fouling of 0.044025°K·m³/kW.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. COP–Coefficient of Performance. Power inputs include compressors and control power.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Table 35. Performance Data - RTWD - 50 Hz- premium efficiency - SI units
Evaporator
Leaving
Water
Temperature
(°C)
Condenser Entering Water Temperature (°C)
25 30 35
kW kW kW kW kW kW
Unit Size Cooling input COP Cooling input COP Cooling input COP
5
160
589.4 95.4 6.2 557.6 106.1 5.2 524.6 118.6 4.4
180
649.7 105.7 6.1 614.2 117.9 5.2 577.1 132.0 4.4
200
699.4 116.1 6.0 661.4 129.7 5.1 621.6 145.5 4.3
7
160
634.4 96.6 6.5 600.9 107.1 5.6 566.2 119.4 4.7
180
699.3 106.9 6.5 662.0 118.8 5.6 623.1 132.6 4.7
200
751.6 117.2 6.4 712.0 130.5 5.4 670.4 146.0 4.6
9
160
681.5 98.0 6.9 646.4 108.2 6.0 609.8 120.3 5.1
180
751.3 108.2 6.9 712.1 119.8 5.9 671.3 133.4 5.0
200
806.1 118.4 6.8 764.7 131.5 5.8 721.3 146.7 4.9
1. Rated in accordance with AHRI Standard 550/590, based on an evaporator temperature drop of 5.6°C, 0.054 L/s per kW on the condenser, evaporator
fouling factor of 0.01761°K·m³/kW and condenser fouling of 0.044025°K·m³/kW.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. COP–Coefficient of Performance. Power inputs include compressors and control power.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Table 34. Performance Data - RTWD - 50 Hz - high efficiency - SI units
Evaporator
Leaving
Water
Temperature
(°C)
Condenser Entering Water Temperature (°C)
25 30 35
kW kW kW kW kW kW
Unit Size Cooling input COP Cooling input COP Cooling input COP