Catalogue

56 RLC-PRC029-EN
Performance Data
Table 33. Performance Data - RTWD - 50 Hz - standard efficiency - SI units
Evaporator
Leaving
Water
Temperature
(°C)
Condenser Entering Water Temperature (°C)
25 30 35
kW kW kW kW kW kW
Unit Size Cooling input COP Cooling input COP Cooling input COP
5
70
257.1 47.8 5.3 242.4 53.5 4.5 226.9 60.0 3.8
80
294.9 55.5 5.3 277.7 62.1 4.4 259.4 69.8 3.7
90
335.2 63.0 5.3 315.6 70.5 4.5 294.5 79.1 3.7
100
356.5 66.8 5.3 336.1 74.8 4.5 314.5 84.0 3.7
110
377.9 70.9 5.3 356.8 79.5 4.5 334.5 89.3 3.7
120
424.5 78.6 5.4 400.6 88.1 4.5 375.3 98.8 3.8
130
461.1 84.3 5.4 435.5 94.5 4.6 408.4 106.0 3.8
140
497.4 92.0 5.4 470.5 102.9 4.6 442.2 115.4 3.8
150
540.6 98.8 5.5 511.9 110.2 4.6 482.1 123.5 3.9
7
70
275.6 48.3 5.7 260.3 54.0 4.8 244.1 60.5 4.0
80
316.2 56.1 5.6 298.3 62.7 4.7 279.3 70.2 4.0
90
359.4 63.7 5.6 339.0 71.1 4.7 317.2 79.6 4.0
100
382.1 67.4 5.6 360.9 75.4 4.8 338.4 84.5 4.0
110
405.0 71.5 5.6 382.9 80.0 4.8 359.5 89.7 4.0
120
455.5 79.5 5.7 430.4 88.8 4.8 403.8 99.3 4.0
130
494.7 85.2 5.8 467.9 95.1 4.9 439.3 106.4 4.1
140
533.5 93.1 5.7 505.2 103.8 4.8 475.6 116.1 4.1
150
580.0 100.0 5.8 549.9 111.3 4.9 518.6 124.4 4.2
9
70
294.9 49.0 6.0 278.9 54.6 5.1 262.0 61.0 4.3
80
338.3 56.8 5.9 319.8 63.3 5.0 300.1 70.8 4.2
90
384.4 64.5 5.9 363.3 71.8 5.0 340.8 80.2 4.2
100
408.7 68.2 6.0 386.7 76.0 5.1 363.2 85.0 4.3
110
433.2 72.2 6.0 410.1 80.6 5.1 385.5 90.2 4.3
120
487.8 80.4 6.0 461.5 89.6 5.1 433.5 99.9 4.3
130
529.7 86.1 6.1 501.6 95.8 5.2 471.6 106.9 4.4
140
571.1 94.3 6.0 541.5 104.8 5.1 510.4 116.9 4.3
150
621.0 101.4 6.1 589.5 112.6 5.2 556.7 125.6 4.4
1. Rated in accordance with AHRI Standard 550/590, based on an evaporator temperature drop of 5.6°C, 0.054 L/s per kW on the condenser, evaporator
fouling factor of 0.01761°K·m³/kW and condenser fouling of 0.044025°K·m³/kW.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. COP–Coefficient of Performance. Power inputs include compressors and control power.
6. Interpolation between points is permissible. Extrapolation is not permitted.