Catalogue

RLC-PRC029-EN 53
Performance Data
Table 30. Part Load Performance – RTWD – 50 Hz – standard efficiency – I-P units
IPLV
Unit Size % Load Tons kW EER kW/ton EER kW/ton
70
100 73.6 53.6 16.5 0.728
22.3 0.539
75 55.2 32.3 20.5 0.585
50 36.8 18.1 24.4 0.492
25 18.4 10.5 21.0 0.568
80
100 84.4 62.2 16.3 0.737
22.4 0.536
75 63.3 37.8 20.1 0.597
50 42.2 21.0 24.1 0.497
25 21.1 10.5 24.1 0.495
90
100 95.9 70.5 16.3 0.735
22.1 0.544
75 71.9 43.1 20.0 0.599
50 48.0 23.7 24.3 0.494
25 24.0 13.5 21.3 0.564
100
100 102.1 74.7 16.4 0.732
22.2 0.540
75 76.6 45.9 20.0 0.600
50 51.0 25.2 24.3 0.493
25 25.5 13.6 22.5 0.534
110
100 108.3 79.3 16.4 0.732
21.7 0.552
75 81.2 49.2 19.8 0.605
50 54.2 27.0 24.1 0.499
25 27.1 16.3 20.0 0.600
120
100 121.7 87.9 16.6 0.722
22.3 0.537
75 91.3 54.9 20.0 0.601
50 60.9 29.6 24.7 0.486
25 30.4 16.3 22.4 0.536
130
100 132.3 94.2 16.9 0.712
22.3 0.537
75 99.3 59.3 20.1 0.597
50 66.2 31.7 25.1 0.479
25 33.1 19.5 20.4 0.591
140
100 142.9 102.8 16.7 0.719
22.3 0.538
75 107.2 64.0 20.1 0.597
50 71.4 34.7 24.7 0.486
25 35.7 19.8 21.6 0.555
150
100 155.5 110.2 16.9 0.709
22.3 0.538
75 116.6 68.2 20.5 0.585
50 77.7 37.9 24.6 0.488
25 38.9 22.7 20.6 0.585
1. Rated in accordance with AHRI Standard 550/590, based on evaporator temperature drop of 10°F, 3 gpm/ton on the condenser, evaporator fouling
factor of 0.0001°F·ft²·h/Btu and condenser fouling factor of 0.00025°F·ft²·h/Btu.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. EER – Energy Efficiency Ratio (Btu/W·h). Power inputs include compressors and control power.