Performance Data
Table 29. Performance Data - RTWD - 50 Hz - premium efficiency - I-P units
Leaving
Water
Temperature
(°F)
Condenser Entering Water Temperature (°F)
75 85 95
Unit kW kW kW
Size Tons input EER kW/ton Tons input EER kW/ton Tons input EER kW/ton
38
160
159.3 92.4 20.6 0.582 149.7 104.1 17.2 0.698 139.8 118.1 14.1 0.848
180
175.6 102.4 20.5 0.586 164.9 115.8 17.0 0.705 153.7 131.6 14.0 0.859
200
189.1 112.5 20.1 0.597 177.7 127.6 16.7 0.720 165.6 145.2 13.7 0.879
40
160
166.1 92.9 21.3 0.562 156.2 104.6 17.9 0.672 146.0 118.4 14.7 0.814
180
183.1 103.0 21.3 0.565 172.1 116.2 17.7 0.678 160.6 131.9 14.6 0.824
200
197.1 113.0 20.9 0.575 185.4 127.9 17.3 0.692 173.0 145.4 14.2 0.843
42
160
173.1 93.6 22.1 0.543 162.9 105.1 18.5 0.647 152.4 118.8 15.3 0.782
180
190.8 103.6 22.0 0.545 179.5 116.7 18.4 0.652 167.7 132.2 15.2 0.791
200
205.3 113.6 21.6 0.555 193.2 128.3 18.0 0.666 180.5 145.6 14.8 0.809
44
160
180.2 94.3 22.8 0.525 169.8 105.6 19.2 0.624 159.0 119.2 15.9 0.753
180
198.7 104.3 22.8 0.527 187.1 117.2 19.1 0.629 174.9 132.5 15.8 0.760
200
213.6 114.2 22.4 0.537 201.3 128.8 18.7 0.642 188.2 145.9 15.4 0.777
46
160
187.6 95.0 23.6 0.509 176.9 106.2 19.9 0.603 165.7 119.7 16.6 0.725
180
206.8 105.0 23.5 0.510 194.9 117.8 19.8 0.606 182.4 132.9 16.4 0.731
200
222.1 114.9 23.1 0.519 209.5 129.3 19.4 0.619 196.2 146.2 16.1 0.747
48
160
195.2 95.8 24.3 0.493 184.2 106.9 20.6 0.583 172.7 120.2 17.2 0.699
180
215.2 105.8 24.3 0.494 202.9 118.4 20.5 0.585 190.1 133.4 17.1 0.704
200
230.8 115.7 23.9 0.503 217.9 129.9 20.1 0.598 204.2 146.6 16.7 0.720
50
160
202.9 96.7 25.1 0.479 191.6 107.6 21.3 0.564 179.8 120.8 17.8 0.674
180
223.7 106.7 25.1 0.479 211.2 119.1 21.2 0.566 198.0 133.9 17.7 0.678
200
239.7 116.5 24.6 0.488 226.5 130.5 20.8 0.578 212.5 147.1 17.3 0.694
1. Rated in accordance with AHRI Standard 550/590, based on evaporator temperature drop of 10°F, 3 gpm/ton on the condenser, evaporator fouling factor of
0.0001°F·ft²·h/Btu and condenser fouling factor of 0.00025°F·ft²·h/Btu.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. EER – Energy Efficiency Ratio (Btu/W·h). Power inputs include compressors and control power.
6. Interpolation between points is permissible. Extrapolation is not permitted.