Catalogue
RLC-PRC029-EN 51
Performance Data
50
60
80.1 39.9 23.8 0.504 75.3 44.9 20.0 0.601 70.4 50.6 16.5 0.726
70
93.9 47.5 23.5 0.510 88.4 53.3 19.8 0.607 82.6 60.1 16.4 0.733
80
107.5 55.1 23.2 0.516 101.3 61.8 19.5 0.614 94.5 69.7 16.2 0.741
90
124.0 63.0 23.5 0.511 116.7 70.5 19.8 0.607 108.9 79.4 16.4 0.733
100
132.4 66.3 23.8 0.504 124.7 74.4 20.0 0.600 116.4 83.8 16.6 0.723
110
141.9 70.1 24.1 0.497 133.7 78.7 20.3 0.592 124.8 88.7 16.8 0.714
120
153.5 76.3 24.0 0.500 144.7 85.7 20.2 0.595 135.2 96.6 16.7 0.717
130
165.0 82.8 23.8 0.504 155.9 93.0 20.0 0.599 145.9 104.8 16.6 0.721
140
179.6 90.2 23.8 0.504 169.7 101.0 20.1 0.597 159.2 113.7 16.7 0.717
160
195.7 97.6 24.0 0.501 185.0 108.9 20.3 0.591 173.9 122.4 17.0 0.707
180
215.8 108.3 23.8 0.504 203.9 121.2 20.1 0.596 191.4 136.4 16.8 0.715
200
236.4 118.3 23.9 0.502 223.5 132.6 20.2 0.595 209.9 149.5 16.8 0.714
220
257.6 133.4 23.1 0.519 244.0 148.1 19.7 0.609 229.6 165.4 16.6 0.722
250
280.8 147.6 22.8 0.527 266.4 162.3 19.7 0.611 251.2 179.8 16.7 0.717
1. Rated in accordance with AHRI Standard 550/590, based on evaporator temperature drop of 10°F, 3 gpm/ton on the condenser, evaporator fouling factor
of 0.0001°F·ft²·h/Btu and condenser fouling factor of 0.00025°F·ft²·h/Btu.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. EER – Energy Efficiency Ratio (Btu/W·h). Power inputs include compressors and control power.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Table 28. Performance Data - RTWD - 50 Hz - high efficiency - I-P units
Evaporator
Leaving
Water
Temperature
(°F)
Condenser Entering Water Temperature (°F)
75 85 95
Unit
Size Tons
kW
Input EER kW/ton Tons
kW
input EER kW/ton Tons
kW
input EER kW/ton