Catalogue
RLC-PRC029-EN 43
Performance Data
Table 24. Performance Data - RTUD - Trane Air-Cooled Condenser - 60 Hz - SI units
Evaporator
Leaving Water
Temperature
(°C)
Condenser Entering Water Temperature (°C)
30 35 40 45
Unit
Size
kW kW kW kW kW kW kW kW
Cooling input COP Cooling input COP Cooling input COP Cooling input COP
5
80
245.8 76.8 3.2 229.2 82.1 2.8 209.6 88.0 2.4 189.2 94.4 2.0
90
298.5 91.8 3.3 279.5 97.9 2.9 257.7 104.6 2.5 234.2 112.0 2.1
100
334.0 102.3 3.3 312.2 109.3 2.9 287.3 117.1 2.5 260.2 125.5 2.1
110
372.7 114.3 3.3 347.7 122.3 2.8 318.6 130.9 2.4 287.3 140.5 2.0
120
404.0 122.7 3.3 378.0 130.8 2.9 348.1 139.9 2.5 316.1 149.8 2.1
130
430.4 128.9 3.3 403.3 137.5 2.9 372.7 147.2 2.5 340.0 157.8 2.2
150
457.4 142.5 3.2 428.6 152.2 2.8 395.6 162.8 2.4 360.0 174.5 2.1
160
494.7 152.0 3.3 464.1 162.3 2.9 429.3 173.7 2.5 391.7 186.2 2.1
180
541.8 166.3 3.3 509.1 177.7 2.9 472.2 190.3 2.5 432.1 204.1 2.1
200
593.9 181.3 3.3 558.7 193.8 2.9 519.3 207.5 2.5 476.4 222.6 2.1
220
649.8 199.5 3.3 611.43 212.7 2.9 567.8 227.5 2.5 521.4 243.7 2.1
250
707.1 218.1 3.2 665.9 232.2 2.9 618.5 247.9 2.5 567.8 265.3 2.1
7
80
262.3 79.1 3.3 245.1 84.5 2.9 224.7 90.4 2.5 203.2 96.9 2.1
90
318.6 94.7 3.4 298.5 100.9 3.0 276.0 107.6 2.6 251.4 115.1 2.2
100
356.5 105.6 3.4 333.3 112.7 3.0 307.3 120.5 2.6 279.2 129.1 2.2
110
397.7 118.2 3.4 371.3 126.2 2.9 340.4 135.0 2.5 308.0 144.6 2.1
120
431.4 126.7 3.4 403.6 134.9 3.0 372.7 144.0 2.6 339.3 154.1 2.2
130
459.5 132.9 3.5 431.1 141.7 3.0 399.1 151.4 2.6 365.0 162.2 2.3
150
488.4 147.0 3.3 458.1 156.7 2.9 423.3 167.5 2.5 386.4 179.3 2.2
160
528.1 156.8 3.4 496.1 167.2 3.0 459.5 178.7 2.6 420.2 191.3 2.2
180
578.0 171.5 3.4 543.6 183.0 3.0 504.9 195.7 2.6 463.4 209.6 2.2
200
633.2 187.0 3.4 596.3 199.5 3.0 554.8 213.3 2.6 510.5 228.5 2.2
220
692.7 206.1 3.4 652.2 219.4 3.0 606.5 234.2 2.6 558.3 250.6 2.2
250
753.8 225.6 3.3 709.9 239.8 3.0 660.3 255.6 2.6 607.2 273.2 2.2
9
80
279.5 81.5 3.4 261.2 87.0 3.0 240.1 92.9 2.6 218.0 99.4 2.2
90
339.7 97.7 3.5 318.2 103.9 3.1 294.6 110.7 2.7 269.3 118.2 2.3
100
379.7 109.1 3.5 355.1 116.3 3.1 328.0 124.1 2.6 298.5 132.8 2.3
110
423.0 122.2 3.5 395.2 130.3 3.0 363.2 139.1 2.6 329.5 148.9 2.2
120
459.5 130.8 3.5 430.7 139.1 3.1 398.0 148.3 2.7 363.2 158.4 2.3
130
489.8 137.1 3.6 459.5 146.0 3.2 426.1 155.8 2.7 390.6 166.7 2.3
150
520.4 151.6 3.4 488.4 161.4 3.0 451.8 172.3 2.6 413.5 184.2 2.2
160
562.9 161.8 3.5 529.5 172.3 3.1 490.8 183.9 2.7 449.7 196.5 2.3
180
615.7 176.9 3.5 579.4 188.5 3.1 538.7 201.2 2.7 495.4 215.2 2.3
200
674.0 192.8 3.5 635.0 205.4 3.1 591.4 219.3 2.7 545.3 234.6 2.3
220
737.0 212.9 3.5 694.4 226.3 3.1 646.6 241.2 2.7 596.0 257.7 2.3
250
801.7 233.5 3.4 755.2 247.7 3.1 702.9 263.6 2.7 647.7 281.3 2.3
1. Rated in accordance with AHRI Standard 550/590, based on an evaporator temperature drop of 5°C, evaporator fouling
factor of 0.01761°K·m³/kW and sea level altitude.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors and control power.
5. COP–Coefficient of Performance. Power inputs include compressors and control power.
6. Interpolation between points is permissible. Extrapolation is not permitted.