Catalogue
42 RLC-PRC029-EN
Performance Data
RTUD 160
100 139.9 10.1
13.53 0.887
75 105.0 12.2
50 70.0 15.2
25 35.0 12.1
RTUD 180
100 153.3 10.1
13.48 0.890
75 115.1 12.4
50 76.7 14.9
25 38.3 12.3
RTUD 200
100 168.1 10.2
13.57 0.884
75 126.2 12.6
50 84.1 15.3
25 42.0 11.0
RTUD 220
100 183.9 10.1
13.48 0.890
75 137.9 12.5
50 92.0 15.1
25 46.0 11.1
RTUD 250
100 200.2 10.1
13.46 0.892
75 150.3 12.6
50 100.2 15.0
25 50.1 11.0
1. Rated in accordance with AHRI Standard 550/590, based on evaporator temperature drop of 10°F, evaporator fouling
factor of 0.0001°F-ft²·h/Btu and Trane air-cooled condenser with an ambient air at 100% of 95°F.
2. Performance is based on 2 pass evaporator configuration.
3. EER - Energy Efficiency Ration (Btu/W·h). Power inputs include compressors and control power.
Table 23. Part Load Performance – RTUD – Trane Air-Cooled Condenser – 60 Hz - I-P units
IPLV
Unit Size % Load Tons EER EER kw/ton