Catalogue

RLC-PRC029-EN 37
Performance Data
Table 21. Performance Data - RTWD - 60 Hz - premium efficiency - SI units
Evaporator
Leaving Water
Temperature
(°C)
Condenser Entering Water Temperature (°C)
25 30 35
kW kW kW kW kW kW
Unit Size Cooling input COP Cooling input COP Cooling input COP
5
150
554.7 91.2 6.1 524.3 101.6 5.1 492.1 113.8 4.3
160
605.5 99.6 6.1 572.8 111.0 5.1 537.8 124.1 4.3
180
658.2 107.5 6.1 623.2 119.5 5.2 586.2 133.5 4.4
200
714.2 116.0 6.1 676.7 128.6 5.2 637.6 143.4 4.4
7
150
597.0 92.2 6.5 565.3 102.4 5.5 531.4 114.2 4.6
160
651.2 100.7 6.4 617.1 111.7 5.5 580.3 124.5 4.6
180
707.7 108.8 6.5 671.1 120.5 5.6 632.2 134.2 4.7
200
767.7 117.6 6.5 728.4 129.9 5.6 687.2 144.4 4.7
9
150
641.3 93.3 6.8 608.2 103.3 5.9 572.7 114.8 5.0
160
698.7 101.8 6.8 663.4 112.7 5.9 624.9 125.2 5.0
180
759.4 110.3 6.9 721.3 121.7 5.9 680.6 135.1 5.0
200
823.9 119.4 6.9 782.6 131.4 5.9 739.4 145.6 5.1
1. Rated in accordance with AHRI Standard 550/590, based on an evaporator temperature drop of 5.6°C, 0.054 L/s per kW on the condenser, evaporator
fouling factor of 0.01761°K·m³/kW and condenser fouling of 0.044025°K·m³/kW.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. COP–Coefficient of Performance. Power inputs include compressors and control power.
6. Interpolation between points is permissible. Extrapolation is not permitted.