Catalogue

36 RLC-PRC029-EN
Performance Data
Table 20. Performance Data - 60 Hz - RTWD - high efficiency - SI units
Evaporator
Leaving Water
Temperature
(°C)
Condenser Entering Water Temperature (°C)
25 30 35
kW kW kW kW kW kW
Unit Size Cooling input COP Cooling input COP Cooling input COP
5
80
284.6 50.1 5.6 268.3 55.7 4.8 250.9 62.2 4.0
90
331.9 57.9 5.7 313.8 64.2 4.9 294.6 71.5 4.1
100
382.1 66.3 5.7 361.0 73.8 4.9 338.8 82.6 4.1
110
432.9 74.7 5.8 408.9 83.5 4.9 383.6 93.7 4.1
120
461.1 79.6 5.8 435.7 89.0 4.9 409.0 99.8 4.1
130
489.8 84.4 5.8 463.1 94.2 4.9 435.1 105.6 4.1
150
533.8 93.3 5.7 505.2 104.1 4.8 474.9 116.6 4.1
160
582.6 101.5 5.7 551.6 113.2 4.9 518.4 126.7 4.1
180
635.5 109.5 5.8 602.2 121.9 4.9 566.9 136.3 4.1
200
690.5 117.5 5.9 654.8 130.5 5.0 617.5 145.7 4.2
220
755.7 132.8 5.7 717.0 147.6 4.8 676.4 164.9 4.1
250
830.9 146.2 5.7 788.0 162.5 4.8 743.0 181.4 4.1
7
80
305.5 50.7 6.0 288.4 56.2 5.1 270.2 62.6 4.3
90
356.1 58.7 6.0 337.1 64.9 5.2 317.0 72.0 4.4
100
410.2 67.1 6.1 388.1 74.5 5.2 364.9 83.1 4.4
110
464.6 75.6 6.1 439.6 84.2 5.2 413.3 94.2 4.4
120
494.9 80.5 6.1 468.5 89.7 5.2 440.7 100.3 4.4
130
525.8 85.3 6.1 498.0 94.9 5.2 468.7 106.1 4.4
150
572.8 94.2 6.1 542.9 104.8 5.2 511.2 117.1 4.4
160
625.1 102.5 6.1 592.8 114.0 5.2 558.0 127.1 4.4
180
681.7 110.8 6.1 647.0 122.9 5.2 610.1 137.0 4.4
200
740.6 119.0 6.2 703.3 131.8 5.3 664.3 146.7 4.5
220
810.1 134.4 6.0 769.7 148.9 5.2 727.2 165.9 4.4
250
891.4 148.0 6.0 846.4 163.9 5.2 799.3 182.4 4.4
9
80
327.2 51.4 6.3 309.4 56.8 5.4 290.4 63.0 4.6
90
381.3 59.7 6.3 361.5 65.7 5.5 340.5 72.6 4.7
100
439.4 68.0 6.4 416.5 75.3 5.5 392.3 83.7 4.7
110
497.4 76.6 6.5 471.6 85.0 5.5 444.3 94.8 4.7
120
530.2 81.6 6.5 502.8 90.5 5.5 473.8 100.9 4.7
130
563.5 86.4 6.5 534.5 95.8 5.6 503.9 106.7 4.7
150
613.4 95.3 6.4 582.3 105.7 5.5 549.1 117.7 4.6
160
669.2 103.7 6.4 635.7 114.9 5.5 599.3 127.8 4.7
180
729.9 112.2 6.5 693.7 124.1 5.6 655.1 137.9 4.7
200
792.9 120.8 6.5 753.9 133.3 5.6 713.1 147.9 4.8
220
866.7 136.3 6.3 824.5 150.5 5.5 780.3 167.1 4.7
250
954.3 150.0 6.3 907.3 165.6 5.5 858.1 183.7 4.7
1. Rated in accordance with AHRI Standard 550/590, based on an evaporator temperature drop of 5.6°C, 0.054 L/s per kW on the condenser, evaporator
fouling factor of 0.01761°K·m³/kW and condenser fouling of 0.044025°K·m³/kW.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. COP–Coefficient of Performance. Power inputs include compressors and control power.
6. Interpolation between points is permissible. Extrapolation is not permitted.