Catalogue
RLC-PRC029-EN 35
Performance Data
Table 19. Performance Data - RTWD - 60 Hz - standard efficiency - SI units
Evaporator
Leaving Water
Temperature
(°C)
Condenser Entering Water Temperature (°C)
25 30 35
kW kW kW kW kW kW
Unit Size Cooling input COP Cooling input COP Cooling input COP
5
80
268.0 50.9 5.2 252.5 56.8 4.4 235.9 63.5 3.7
90
306.2 58.0 5.2 289.8 64.7 4.5 272.4 72.3 3.7
100
350.3 66.9 5.2 331.3 74.9 4.4 311.1 84.0 3.7
110
396.8 75.8 5.2 375.0 85.1 4.4 352.0 95.7 3.7
120
435.0 81.8 5.3 411.1 91.6 4.5 386.0 102.9 3.7
130
462.6 87.3 5.3 437.4 97.7 4.5 410.9 109.6 3.7
140
505.4 95.9 5.2 477.9 107.1 4.4 449.0 120.0 3.7
7
80
287.5 51.6 5.5 271.2 57.3 4.7 253.9 63.9 3.9
90
327.8 58.8 5.5 310.6 65.2 4.7 292.5 72.6 4.0
100
375.0 67.7 5.5 355.2 75.5 4.7 334.2 84.4 3.9
110
424.8 76.6 5.5 402.1 85.7 4.7 378.2 96.2 3.9
120
466.4 82.8 5.6 441.4 92.4 4.8 415.2 103.5 4.0
130
496.0 88.4 5.6 469.6 98.6 4.7 441.9 110.3 4.0
140
542.1 97.0 5.6 513.4 108.0 4.7 483.0 120.6 4.0
9
80
307.7 52.3 5.8 290.7 57.9 5.0 272.6 64.4 4.2
90
350.2 59.6 5.8 332.3 65.9 5.0 313.4 73.2 4.3
100
400.7 68.5 5.8 380.1 76.2 5.0 358.3 85.0 4.2
110
453.8 77.6 5.8 430.3 86.5 5.0 405.5 96.8 4.2
120
499.1 83.9 5.9 473.1 93.4 5.0 445.8 104.3 4.3
130
530.8 89.6 5.9 503.3 99.7 5.0 474.4 111.2 4.3
140
580.4 98.4 5.9 550.3 109.2 5.0 518.4 121.5 4.3
1. Rated in accordance with AHRI Standard 550/590, based on an evaporator temperature drop of 5.6°C, 0.054 L/s per kW on the condenser, evaporator
fouling factor of 0.01761°K·m³/kW and condenser fouling of 0.044025°K·m³/kW.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. COP–Coefficient of Performance. Power inputs include compressors and control power.
6. Interpolation between points is permissible. Extrapolation is not permitted.