Catalogue

32 RLC-PRC029-EN
Performance Data
Table 16. Part Load Performance – 60 Hz – standard efficiency – I-P units
IPLV
Unit Size % Load Tons kW EER kW/ton EER kW/ton
80
100 76.7 57.0 16.2 0.742
21.6 0.557
75 57.5 35.2 19.6 0.611
50 38.4 19.3 23.9 0.502
25 19.2 11.6 19.9 0.602
90
100 87.9 64.8 16.3 0.737
21.5 0.558
75 65.9 39.7 19.9 0.603
50 43.9 22.3 23.7 0.508
25 22.0 13.4 19.7 0.609
100
100 100.5 74.8 16.1 0.745
21.6 0.554
75 75.3 46.4 19.5 0.615
50 50.2 25.6 23.6 0.509
25 25.1 16.7 18.0 0.538
110
100 113.8 84.9 16.1 0.747
21.3 0.563
75 85.3 53.0 19.3 0.622
50 56.9 28.7 23.8 0.505
25 28.4 17.3 19.7 0.609
120
100 124.8 91.5 16.4 0.733
21.8 0.551
75 93.6 57.5 19.5 0.614
50 62.4 31.1 24.1 0.498
25 31.2 17.6 21.3 0.563
130
100 132.8 97.6 16.3 0.735
21.3 0.564
75 99.6 61.5 19.4 0.618
50 66.4 33.6 23.7 0.506
25 33.2 20.9 19.1 0.630
140
100 145.2 107.0 16.3 0.737
21.5 0.558
75 108.9 68.6 19.0 0.630
50 72.6 36.1 24.1 0.497
25 36.3 20.9 20.8 0.576
1. Rated in accordance with AHRI Standard 550/590, based on evaporator temperature drop of 10°F, 3 gpm/ton on the condenser, evaporator
fouling factor of 0.0001°F·ft²·h/Btu and condenser fouling factor of 0.00025°F·ft²·h/Btu.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. EER – Energy Efficiency Ratio (Btu/W·h). Power inputs include compressors and control power.