Catalogue

30 RLC-PRC029-EN
Performance Data
48
80
93.7 50.3 22.2 0.541 88.2 56.1 18.7 0.641 82.2 63.0 15.6 0.771
90
109.2 58.4 22.3 0.538 103.0 64.9 18.9 0.634 96.4 72.5 15.9 0.756
100
125.9 66.5 22.6 0.532 118.7 74.4 19.0 0.630 111.1 83.6 15.9 0.756
110
142.5 74.8 22.7 0.528 134.4 83.9 19.1 0.628 125.8 94.8 15.9 0.757
120
151.8 79.7 22.7 0.528 143.3 89.4 19.1 0.627 134.2 100.9 15.9 0.755
130
161.4 84.4 22.8 0.526 152.3 94.6 19.2 0.624 142.7 106.7 16.0 0.750
150
175.6 93.2 22.5 0.533 165.9 104.5 19.0 0.632 155.5 117.7 15.8 0.759
160
191.5 101.3 22.6 0.531 181.1 113.5 19.1 0.629 169.7 127.8 15.9 0.755
180
208.9 109.7 22.8 0.527 197.6 122.6 19.3 0.623 185.5 137.9 16.1 0.745
200
226.9 118.2 23.0 0.523 214.8 131.7 19.5 0.615 201.9 147.8 16.3 0.734
220
248.1 133.3 22.3 0.539 234.9 148.7 18.9 0.635 221.0 167.0 15.8 0.758
250
273.2 146.8 22.3 0.539 258.5 163.6 18.9 0.635 243.0 183.6 15.8 0.757
50
80
97.3 50.7 22.8 0.525 91.6 56.5 19.3 0.621 85.5 63.3 16.1 0.744
90
113.3 59.0 22.9 0.524 107.0 65.4 19.5 0.615 100.3 72.9 16.4 0.731
100
130.6 67.1 23.2 0.517 123.3 74.9 19.7 0.610 115.6 84.0 16.4 0.730
110
147.8 75.5 23.4 0.513 139.6 84.5 19.7 0.608 130.9 95.2 16.4 0.731
120
157.6 80.4 23.4 0.512 148.9 89.9 19.8 0.607 139.6 101.3 16.5 0.729
130
167.6 85.1 23.5 0.510 158.3 95.2 19.9 0.604 148.4 107.1 16.6 0.724
150
182.2 93.9 23.2 0.517 172.4 105.0 19.6 0.612 161.7 118.1 16.4 0.733
160
198.7 102.0 23.3 0.515 188.1 114.1 19.7 0.609 176.4 128.2 16.5 0.729
180
216.8 110.6 23.4 0.512 205.3 123.4 19.9 0.603 192.9 138.5 16.7 0.720
200
235.5 119.3 23.6 0.508 223.1 132.6 20.1 0.596 209.9 148.6 16.9 0.710
220
257.3 134.5 22.9 0.524 243.8 149.7 19.5 0.615 229.6 167.8 16.4 0.732
250
283.5 148.0 22.9 0.524 268.4 164.6 19.5 0.615 252.6 184.4 16.4 0.732
1. Rated in accordance with AHRI Standard 550/590, based on evaporator temperature drop of 10°F, 3 gpm/ton on the condenser, evaporator fouling
factor of 0.0001°F·ft²·h/Btu and condenser fouling factor of 0.00025°F·ft²·h/Btu.
2. Performance is based on 2 pass evaporator configuration.
3. Consult Trane representative for additional performance information.
4. kW input is for compressors only.
5. EER – Energy Efficiency Ratio (Btu/W·h). Power inputs include compressors and control power.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Table 14. Performance Data - RTWD - 60 Hz - high efficiency - I-P units
Evaporator
Leaving Water
Temp (°F)
Condenser Entering Water Temperature (°F)
75 85 95
Unit kW kW kW
Size Tons input EER kW/ton Tons input EER kW/ton Tons input EER kW/ton