Catalogue

RLC-PRC029-EN 25
General Data
Table 12. General Data – RTWD – 50 Hz – premium efficiency
Size 160 180 200
Compressor
Quantity 222
Evaporator
2 Pass Arrangement
Water Conn. SizeNPS666
(mm) 150 150 150
Water Storage (gal) 29.3 31.3 31.8
(L) 110.9 118.3 120.3
Minimum Flow (gpm) 187 202 240
(L/s) 11.8 12.7 15.1
Maximum Flow (gpm) 683 739 879
(L/s) 43.1 46.7 55.5
3 Pass Arrangement
Water Conn. SizeNPS444
(mm) 100 100 100
Water Storage (gal) 28.6 30.6 31.0
(L) 108.3 115.7 117.5
Minimum Flow (gpm) 125 135 160
(L/s) 7.8 8.5 10.1
Maximum Flow (gpm) 455 492 586
(L/s) 28.7 31.1 37.0
Condenser
Water Conn. SizeNPS666
(mm) 150 150 150
Water Storage (gal) 30.0 34.5 39.2
(L) 113.4 130.6 148.3
Minimum Flow (gpm) 206 245 326
(L/s) 13.0 15.4 20.5
Maximum Flow (gpm) 754 895 1192
(L/s) 47.6 56.5 75.3
General Unit
Refrigerant Type R-134a R-134a R-134a
# Refrig Circuits 2 2 2
Refrigerant Charge (lb) 176.4/176.4 174.2/178.6 176.4/174.2
(kg) 80/80 79/81 80/79
Oil Charge (qt) 10.5/10.5 10.5/12.4 12.4/12.4
(L) 9.9/9.9 9.9/11.7 11.7/11.7
1. Data containing information on two circuits is shown as circuit 1/circuit 2.
2. Flow limits are for water only.