Catalogue

RLC-PRC029-EN 21
General Data
Table 8. General Data – Condenser by Trane – 60 Hz (continued)
Size 150 160 180 200 220 250
Condenser
Condenser Quantity 222222
Fins/Inch¹ 8/12 12/12 12/8 8/8 8/10 10/10
Coil Length¹ (inch) 162/162 162/162 162/216 216/216 216/216 216/216
4115/4115 4115/4115 4115/5486 5486/5486 5486/5486 5486/5486
Coil Width¹ (inch) 85/85 85/85 85/85 85/85 85/85 85/85
2159/2159 2159/2159 2159/2159 2159/2159 2159/2159 2159/2159
Number of Rows 3/3 3/3 3/3 3/3 3/4 4/4
Condenser Fans
Fan Quantity¹ 6/6 6/6 6/8 8/8 8/8 8/8
Diameter (inch) 30 30 30 30 30 30
Nominal RPM (rpm) 850 850 850 850 850 850
Air Flow¹ (cfm)
60,954/
56,646
56,646/
56,646
56,646/
81,272
81,272/
81,272
81,272/
72,248
72,248/
72,248
Tip Speed (fpm) 6676 6676 6676 6676 6676 6676
Motor HP(hp)1.51.51.51.51.51.5
General
Recommended Refrigerant
Charge²,³
(lbs) 76/76 76/76 76/101 101/101 101/134 134/134
(kg) 34.5/34.5 34.5/34.5 34.5/45.8 45.8/45.8 45.8/60.8 60.8/60.8
Discharge/Liquid Connection
Diameters
(inch) 2.125 2.125 2.125 2.125 2.125 2.125
(mm) 54 54 54 54 54 54
1. Data containing information on two condensers is shown as cond 1/cond 2.
2. Data containing information on two circuits is shown as circuit 1/circuit 2.
3. Condenser is not factory charged, the refrigerant must be purchased and charged in the field.