Catalogue

20 RLC-PRC029-EN
General Data
Table 7. General Data – Condenser by Trane – 60 Hz
Size 80 90 100 110 120 130
Condenser
Condenser Quantity 111111
Fins/Inch 12 10 10 12 8 10
Coil Length (inch) 162 216 216 216 270 270
(mm) 4115 5486 5486 5486 6858 6858
Coil Width(inch)858585858585
(mm) 2159 2159 2159 2159 2159 2159
Number of Rows 334444
Condenser Fans
Fan Quantity 6 8 8 8 10 10
Diameter (inch) 30 30 30 30 30 30
(mm) 762 762 762 762 762 762
Nominal RPM (rpm) 850 850 850 850 850 850
Air Flow (cfm) 56,646 78,280 72,248 69,280 94,490 90,310
Tip Speed (fpm) 6676 6676 6676 6676 6676 6676
Motor HP(hp)1.51.51.51.51.51.5
General
Recommended Refrigerant
Charge¹
(lbs) 40/40 52/52 68/68 68/68 85/85 85/85
(kg) 18.1/18.1 23.6/23.6 30.8/30.8 30.8/30.8 38.6/38.6 38.6/38.6
Discharge/Liquid Connection
Diameters
(inch)2.12.12.12.12.12.1
(mm) 54 54 54 54 54 54
1. Data containing information on two circuits is shown as circuit 1/circuit 2.
2. Condenser is not factory charged, the refrigerant must be purchased and charged in the field.