16 RLC-PRC029-EN
General Data
Table 3. General Data – RTWD – 60 Hz – high efficiency (continued)
Size 150 160 180 200 220 250
Compressor
Quantity 222222
Evaporator
2 Pass Arrangement
Water Conn. Size NPS 5 5 5 5 6 6
mm 125 125 125 125 150 150
Water Storage (gal) 19.2 20.3 22.3 24.2 28.6 31.8
(L) 72.6 77.0 84.5 91.5 108.3 120.3
Minimum Flow (gpm) 141 151 170 187 211 240
(L/s) 8.9 9.5 10.7 11.8 13.3 15.1
Maximum Flow (gpm) 515 554 621 683 772 879
(L/s) 32.5 35.0 39.2 43.1 48.8 55.5
3 Pass Arrangement
Water Conn. Size NPS 4 4 4 4 4 4
mm 100 100 100 100 100 100
Water Storage (gal) 18.8 20.0 22.0 23.8 27.9 31.0
(L) 71.2 75.6 83.2 90.1 105.5 117.5
Minimum Flow (gpm) 94 101 113 124 141 160
(L/s) 5.9 6.4 7.1 7.8 8.9 10.1
Maximum Flow (gpm) 343 369 414 455 515 586
(L/s) 21.7 23.3 26.2 28.7 32.5 37.0
Condenser
Water Conn. Size NPS 6 6 6 6 6 6
mm 150 150 150 150 150 150
Water Storage (gal) 21.6 22.9 24.6 26.2 31.1 39.2
(L) 81.7 86.8 93.0 99.2 117.8 148.3
Minimum Flow (gpm) 160 173 190 206 245 326
(L/s) 10.1 10.9 12.0 13.0 15.4 20.5
Maximum Flow (gpm) 583 634 694 754 895 1192
(L/s) 36.8 40.0 43.8 47.6 56.5 75.3
General Unit
Refrigerant Type R-134a R-134a R-134a R-134a R-134a R-134a
# Refrig Circuits 222222
Refrigerant Charge (lb) 134.5/143.3 141.1/141.1 138.9/138.9 136.7/136.7 178.6/185.2 180.8/180.8
(kg) 61/65 64/64 63/63 62/62 81/84 82/82
Oil Charge (qt) 10.5/12.4 12.4/12.4 12.4/12.4 12.4/12.4 12.4/12.4 12.4/12.4
(L) 9.9/11.7 11.7/11.7 11.7/11.7 11.7/11.7 11.7/11.7 11.7/11.7
1. Data containing information on two circuits is shown as circuit 1/circuit 2.
2. Flow limits are for water only.