Catalogue
RLC-PRC029-EN 15
General Data
Table 2. General Data – RTWD – 60 Hz – high efficiency
Size 80 90 100 110 120 130
Compressor
Quantity 222222
Evaporator
2 Pass Arrangement
Water Conn. Size NPS 4 4 4 5 5 5
mm 100 100 100 125 125 125
Water Storage (gal) 9.8 11.9 12.8 15.3 16.4 17.3
(L) 37.0 45.2 48.3 57.9 62.3 65.4
Minimum Flow (gpm) 72 92 100 112 123 130
(L/s) 4.5 5.8 6.3 7.0 7.7 8.2
Maximum Flow (gpm) 263 336 364 409 448 476
(L/s) 16.6 21.2 23.0 25.8 28.3 30.0
3 Pass Arrangement
Water Conn. Size NPS 3 3 3 4 4 4
mm 80 80 80 100 100 100
Water Storage (gal) 9.8 11.9 12.8 15.3 16.4 17.3
(L) 37.0 45.2 48.3 57.9 62.3 65.4
Minimum Flow(gpm)486167758287
(L/s) 3.0 3.9 4.2 4.7 5.1 5.5
Maximum Flow (gpm) 175 223 242 271 298 316
(L/s) 11.1 14.1 15.3 17.2 18.8 20.0
Condenser
Water Conn. Size NPS 5 5 5 5 5 5
mm 125 125 125 125 125 125
Water Storage (gal) 11.9 12.7 14.9 16.6 17.2 18.0
(L) 45.1 48.1 56.3 62.7 65.2 68.3
Minimum Flow (gpm) 87 95 117 130 136 145
(L/s) 5.5 6.0 7.4 8.1 8.6 9.1
Maximum Flow (gpm) 317 347 427 473 498 528
(L/s) 20.0 21.9 27.0 29.9 31.4 33.3
General Unit
Refrigerant Type R-134a R-134a R-134a R-134a R-134a R-134a
# Refrig Circuits 222222
Refrigerant Charge (lb) 99.2/99.2 97/97 123.5/125.7 123.5/123.5 121.3/121.3 119/119
(kg) 45/45 44/44 56/57 56/56 55/55 54/54
Oil Charge (qt) 7.2/7.2 7.2/7.2 7.2/10.5 10.5/10.5 10.5/10.5 10.5/10.5
(L) 6.8/6.8 6.8/6.8 6.8/9.9 9.9/9.9 9.9/9.9 9.9/9.9
1. Data containing information on two circuits is shown as circuit 1/circuit 2.
2. Flow limits are for water only.