Catalogue

RLC-PRC029-EN 135
Options
All necessary settings and setpoints are programmed into the microprocessor-based controller via
the operator interface. The controller is capable of receiving signals simultaneously from a variety
of control sources, in any combination, and priority order of control sources can be programmed.
The control source with priority determines active setpoints via the signal it sends to the control
panel. Control sources may be:
Local operator interface (standard)
Time of day scheduling (optional capability available from local operator interface)
Hard-wired 4-20 mA or 2-10 Vdc signal from an external source (interface optional; control
source not supplied)
LonTalk™ LCI-C (interface optional; control source not supplied)
Trane Tracer Summit
system (interface optional; control source not supplied)
Quality Assurance
The quality management system applied by Trane has been subject to independent third-party
assessment and approval to ISO 9001. The products described in this catalog are designed,
manufactured and tested in accordance with the approved system requirements described in the
Trane Quality Manual.
Options
Base Rail Forklifting
Channels built into the base frame allow for easy movement using a forklift
Dual Relief Valve
Unit comes with dual relief valves on both the high pressure side and low pressure side of each
refrigerant circuit. Each dual relief valve configuration includes an isolation valve. Single relief
valves are standard.
Flanged Water Connection Kit
Kit to convert all four water connections (RTWD units) or two water connections (RTUD units) from
grooved pipe to flanged connections. This includes: grooved couplings, pipe offsets, and grooved
to flange adapters.
Factory Installed Flow Switches
Factory installed IMF effector flow switches for the evaporator and/or condenser.
High-Temperature Condenser
Optimized compressors, oil cooler and high condenser temperature control panel allows for
leaving condenser water temperatures up to 140°F (60°C). This option is required for entering
condenser water temperatures above 95°F (35°C).
Insulation
The evaporator, water boxes, and motor housing are covered with factory installed 0.75 inch (19.05
mm) insulation. Factory installed foam insulation is used on the suction line, liquid level sensor,
oil return system assembly (with its associated piping).