Catalogue

134 RLC-PRC029-EN
Mechanical Specifications
The panel includes machine protection shutdown requiring manual reset for the following
conditions:
Low evaporator refrigerant temperature and pressure
High condenser refrigerant pressure
Low oil flow
Critical sensor or detection circuit faults
Motor current overload
High compressor discharge temperature
Lost communication between modules
Electrical distribution faults: phase loss, phase imbalance, or phase reversal
External and local emergency stop
Starter transition failure
The panel also includes machine protection shutdown with automatic reset for the following
correctable conditions:
Momentary power loss
Under/over voltage
Loss of evaporator or condenser water flow
When a fault is detected, the control system conducts more than 100 diagnostic checks and displays
results. The display will identify the fault, indicate date, time, and operating mode at time of
occurrence, and provide type of reset required and a help message.
Clear Language Display Panel
Factory-mounted to the control panel door, the operator interface has an LCD touch-screen display
for operator input and information output. This interface provides access to the following
information: evaporator report, condenser report, compressor report, ASHRAE Guideline 3 report,
operator settings, service settings, service tests, and diagnostics. All diagnostics and messages are
displayed in clear un-coded language.
Data contained in available reports includes:
Water and air temperatures
Refrigerant levels and temperatures
Oil pressure
Flow switch status
•EXV position
Head pressure control command
Compressor starts and run-time
Line phase percent RLA, amps, and volts