Catalogue

RLC-PRC029-EN 123
Dimensions
Table 64. RTWD – 50 Hz Dimensions – 70-150 ton SE, 60-120 ton HE
RTWD Standard Efficiency High Efficiency
70,80,90,100,110
inch/mm
120,130,140,150
inch/mm
60,70,80
inch/mm
90,100,110,120
inch/mm
A (2 pass evap)
138.2/3510 138.8/3525 126.4/3210 127.0/3225
B (3 pass evap)
145.5/3620 145.5/3620 130.7/3320 130.7/3320
C
75.9/1929 76.9/1955 76.1/1933 76.1/1933
D
34.3/871 34.8/884 35.1/890 35.1/890
E
23.6/600 23.6/600 23.6/600 23.6/600
F
9.1/231 9.1/231 9.1/231 9.1/231
G
27.9/709 27.9/709 27.9/709 27.9/709
H
36.6/929 36.6/929 36.6/929 36.6/929
J (2 pass evap)
11.0/280 10.6/268 10.7/273 10.2/259
J (3 pass evap)
10.4/265 10.1/256 10.2/259 9.7/247
K (2 pass evap)
18.9/479 19.2/487 18.6/473 18.9/479
L (3 pass evap)
19.5/495 19.5/496 19.2/487 19.2/487
M
36/914 36/914 36/914 36.0/914
N*
36/914* 36/914* 36/914* 36/914*
R
127/3226 127/3226 115/2921 115/2921
S
36/914 36/914 36/914 36.0/914
Reference
1
Evaporator Water Inlet
2
Evaporator Water Outlet
3
Condenser Water Inlet
4
Condenser Water Outlet
5
Power Disconnect
6
Power Wire
7
Control Wire
8
Control Panel
9
Condenser Return Waterbox End - Minimum Clearance (for tube removal)
10
Condenser Supply Waterbox End - Minimum Clearance (for maintenance)
11
Condenser
12
Evaporator
13
Panel Power Section [door swing 31.3 inch (796.9 mm)]
14
Panel Power Section [door swing 31.1 inch (790.1 mm)]
15
Panel Control Section [door swing 22.4 inch (568.14 mm)]
II
2 Pass Evaporator Unit
III
3 Pass Evaporator Unit
*
42 inch (1067 mm) clearance required to other ground parts, two units with panels facing each other or other live parts
require a clearance of 48 inch (1220 mm)